Single channel controllers specifications, Ordering information – Sierra Monitor Corporation 4001 User Manual

Page 2

Advertising
background image

Single Channel Controllers

SPECIFICATIONS

INPUT SIGNAL:

Standard: 4-20mA
Factory Options: 0-5V, 0-10 V, 0-20mA

INPUT

The input loop resistance for the 4-20mA

RESISTANCE:

loop is 100 ohms

INPUT POWER:

Model 4001

18-24 VDC, Nominal 350 mA, Max. 500 mA.
Battery charger feature accepts 120V AC

Model 4011

14-30 VDC, Nominal 100 mA @24VDC
without sensor module, 180 mA @20VDC
with sensor module at 20 mA loop current

ALARM LEVELS:

Two alarms, user adjustable, alarm levels
HiHi, HiLo, or LoLo

ALARM

Jumper selectable for Latching/Non-

CONFIGURATION:

Latching. Jumper selectable for Alarming
on GREATER or LESS than Alarm Level.

TROUBLE RELAY:

Relay de-energizes when loop current is
less than 3 mA or when power is removed.

RELAY RATING:

SPDT Form C, 28VDC @ 5 Amp (fused),
120 VAC @ 4 Amp

ALARM ACKNOWLEDGE:

Model 4001

External alarm reset available - resets
latched relays. Alarm relays reset but alarm
status LEDs will track actual condition.

Model 4011

Front panel push-button or external alarm
reset will reset alarm relays programmed
for Latching. Alarm relays reset but alarm
status LEDs will track actual condition.

Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-6611 800-727-4377 FAX: (408) 262-9042

Visit our web site: www.sierramonitor.com E-Mail: [email protected]

DISPLAY:

3 1/2 digit liquid crystal

RECORDER

0-2 VDC with RL=1000 ohms minimum.

OUTPUT:

Output proportional to display. Power available
is 12VDC @ 5OmA

CHARGER OUTPUT 12 VDC Trickle Charge for battery back-up
(Model 4001):

ENCLOSURE:

Model 4001

NEMA 4X (NEMA 7 optional)
11.5"H x 8.0"W x 6.9"D (29.2 x 20.3 x 17.5 cm)
11.2 lbs (5.1 Kg)

Model 4011

1/8 DIN
1.9"H x 3.8"W x 7.3"D (4.8 x 9.6 x 18.5 cm)
1.2 lbs (0.5 Kg)

ORDERING INFORMATION

4001-01

Model 4001 Controller, DC, NEMA 4X

4001-11

Model 4001 Controller, AC, NEMA 4X

4001-12

Model 4001 Controller, AC, NEMA 7

4011-00

Model 4011 Controller, DC, DIN

(Adding SPM69155 Power Supply converts AC
power to DC input to the 4011-00)

4346-01

Power Supply/Battery Back-up for 4011

SPM69155

Power Supply AC/DC for 4011 (plugs in
wall socket)(1 unit)

Model 4001

Model 4011

@ l997 by Sierra Monitor Corporation Printed in USA