Bobcat Model B-120A and B-200A

11

DIAGNOSTIC ERROR CODES

WARNING:
If an operational problem has occurred, the boiler will
shut off and show an “A”, “E” or “H” in the mode display,
along with an error code in the temperature display.
Do not attempt performing any service under these
conditions, but do note the mode and temperature dis-
play indication, in case the problem clears itself. An “A”
indication error can be cleared by pressing the reset
button once, which will allow re-try of operation. Do not
repeatedly press the reset button in this case, or if an
“E” or “H” indication error is displayed. Call a trained,
experienced service technician to troubleshoot and cor-
rect the problem. The Bobcat Installation and Operating
Instructions, publication B-40 contain a full troubleshoot-
ing section for this. Turn off all electric power ot the boil-
er before service.

A. LOCKOUT ERRORS:

Indicated by an “A” in the mode display. The reset
button must be pressed to clear the error and retry
operation. The temperature display shows the error
code.

B. BLOCKING ERRORS:

Indicated by an “E” in the mode display. Operation is
automatically restored, once the condition returns to
normal or is fixed. The temperature display shows
the error code. Pressing the “Reset” button is not
required.

C. WARNING ERRORS:

Indicated by an “H” in the mode display. Operation
of the space heating mode is not affected, and the
warning is displayed intermittently. Operation of the
DHW mode is automatically restored, once the
condition is fixed. The temperature display shows
the error code. Pressing the “Reset” button is
not required.

ERROR

CODE

INDICATION

01

Ignition Failure - 3 unsuccessful ignition

attempts in a row

02

Flame Failure - 3 losses of flame signal

during one demand

03

Water High Limit Open

04, 05, 09,
10, 12, 13,
14, 15, 16,

18, 32

Control Failure

19, 20

Flame Detected at Wrong Time

33

Fan Failure - RPM Error

ERROR

CODE

INDICATION

01

Water Outlet Sensor Open

02

Water Inlet Sensor Open

03

Flue Gas Sensor Open

11

Water Outlet Sensor Shorted

12

Water Inlet Sensor Shorted

13

Flue Gas Sensor Shorted

19, 42,
45, 46,

47, 48

Control Failure

20

Flame Detected at Wrong Time

21

Polarity Error

22

Frequency Error

24

Earth Connection Faulty

30

Excess Flue Temperature

31

Low Water Cutoff Error

32

Excess Water Inlet Temperature

51

Reset Button Error

52

Boiler Model Selection Error

ERROR

CODE

INDICATION

04

Domestic Hot Water Tank Sensor Open

14

Domestic Hot Water Tank Sensor Shorted