Condensate piping – State SHE50 100 User Manual

Page 19

Advertising
background image

19

54) or the Natural Gas and Propane Installation Code (CAN/CSA

B149.1) whichever applies. Copper or brass tubing and fittings

(except tin lined copper tubing) shall not be used.
If the gas control valve is subjected to pressures exceeding 1/2 psi

(3.5 kPa), the damage to the gas control valve could result in a fire

or explosion from leaking gas.
If the main gas line Shut-off serving all gas appliances is used, also

turn “off” the gas at each appliance. Leave all gas appliances shut

“off” until the water heater installation is complete.
A gas line of sufficient size must be run to the water heater. Consult

the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA

54) or the Natural Gas and Propane Installation Code (CAN/CSA

B149.1) and your gas supplier concerning pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A sediment trap ahead of the gas control valve to help prevent dirt

and foreign materials from entering the gas control valve.

• A ground joint union of proper size between the shut off valve and

control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

condensate pIpInG

This water heater is a condensing unit and requires a drain to be

located in close proximity to allow the condensate to drain safely.

The condensate drains from the unit at the exhaust tee located at

the bottom of the unit (see figure 12). Condensate from this water

heater is mildly acidic. Please note that some local codes require

that condensate is treated by using a pH neutralizing filter prior to

disposal.
Caution must be used to ensure that the drain is free and clear of

debris and will not allow backflow through the condensate hose.

Consideration must be given to avoid freezing of the condensate

lines which could result in excessive build up of condensate inside

the water heater. Waterproof heat tape may be required to prevent

freezing of the condensate lines. Please ensure that the outlet of the

condensate drain does not create a slippery condition which could

lead to personal injury.

CONDENSATION WARNING: THIS WATER HEATER IS A

CONDENSING UNIT AND REqUIRES A DRAIN TO BE LOCATED

IN CLOSE PROXIMITY TO ALLOW CONDENSATE TO DRAIN

SAFELY. THE CONDENSATE DRAINS FROM UNIT AT THE

EXHAUST ELBOW LOCATED AT BOTTOM OF UNIT. NOTE:

IT IS IMPORTANT THAT THE CONDENSATE HOSE NOT BE

ELEvATED ABOvE THE EXHAUST ELBOW, SEE FIGURE 12.

CONDENSATE BUILD-UP WILL BLOCk THE EXHAUST OUTLET,

WHICH WILL CAUSE IMPROPER OPERATION.

fIGure 12.

the condensate drain line must be routed to a suitable drain. If

no floor drain is available or the drain is above the level of the

condensate line, install a condensate pump that is resistant

to the acidic condensate. these pumps are available from

local distributors. If the pump is not resistant to acidic water,

a condensate neutralizer must be used ahead of the pump.

when installing the drain line, note the following:
• Plastic pipe or tubing must be used to connect the condensate

drain to a suitable drain or condensate pump. Do not use

copper tubing, iron, or steel pipe for the condensate drain line.

• Condensate drain lines should be installed in conditioned

areas only. Drain lines installed in areas that are subject to

freezing temperatures should be wrapped with a nationally

recognized/listed heat tape and/or approved insulation for

freeze protection. Install per manufacturer’s instructions.

• Do not common drain with the temperature and pressure relief

valve or the condensate line from an air conditioner evaporator coil.

• Slope the condensate drain toward the inside floor drain or

condensate pump.

• The condensate drain line and connection to the drain piping

must comply with all local codes.

hIGh altItude InstallatIons

This high efficiency water heater is certified for use without

modification for an altitude of 10,000 feet (3,079 meters). Consult

the factory for installation at altitudes over 10,100 feet (3,079m).
Some gas utility companies derate their gas for altitude, making

it unnecessary to install high altitude orifices. Call the local gas or

utility company to verify BTU content.
Due to the input ration reduction at high altitudes, the output rating

of the appliance is also reduced and should be compensated for in

the sizing of the equipment for applications.

Advertising