Digital access keypad manual, Seco-larm u.s.a., inc, Page 3 page 6 – SECO-LARM USA Enforcer SK-1011-SQ User Manual

Page 3

Advertising
background image

Digital Access Keypad Manual

SECO-LARM U.S.A., Inc.

Digital Access Keypad Manual

(DEFAULT: )

Power:
• Operation voltage -- 12-24 Volts AC/DC. No jumper needed to set voltage.

• Stand-by current drain -- 10mA @12VDC.

• Active current drain (press keypad key) -- Under 30mA.
• Active current drain (relay activated) -- Under 80mA.
Outputs:
• Relay output -- 5A @ 28VDC, Form "C", N.O./C./N.C., programmable for 1 to 999 second timed output or

shunt (start/stop) output. Three terminals.

• Tamper output -- 50Ma @12VDC, N.C. output. Connect to tamper circuit of alarm control panel.

Two terminals.

Inputs:
• Power -- 12-24Volts AC/DC. Two terminals.
• Egress -- N.O., ground (-). Single terminal.
Code Operation:
• Up to 100 user codes, 10,000 possible user code combinations.

• Max. 10 seconds to enter each digit.
• Max. 30 seconds to enter each code.
Dimensions (keypad with back box):
• 4-5/8" x 2-7/8" x 1-7/8" (117 x 74 x 48 mm).
Weight (keypad with back box):
• 6.3 oz. (180 grams).

SPECIFICATIONS:

WIRING (SAMPLE INSTALLATION):

USER CODE WORKSHEET

OUTPUT 1

EG

N.C.

(+) (--)

(for DC

use only)

Egress button (inside the

protected premises)

(+)

N.C. N.O.

12~24V AC/DC

C.

12VDC

power

supply

+

--

Electric

Lock

Diode

1N4004

Cathode

N.O.

Additional egress buttons

can be connected in parallel

as needed

N.O.

REMARKS:

Output relay

N.O. output for fail-secure lock.

N.C. output for fail-safe lock.

OR

+

--

Tamper

N.C.

Connect to the N.C.

24hr. zone of alarm

panel or other

signalling device.

N.O.

#

#

8 4

1

0

Enter Master code

*Key in the Master Code.
Note: For first-time use, Master code is

Confirm

Func ion

Enter into programming mode

Enter Programming Mode

Data Refresh

Configure Relay Outputs

Op ion

Confirm

Function

Clears all previously stored data.

Option Output ime

1 to 999

Confirm

Function

Relay momentary mode, from 1 to 999 seconds
Relay shunt mode (ON/OFF)

X X X X

*

0 0 0 0

#

#

#

8 9 0 1

4 0

*

INSTALLER PROGRAMMING

These functions should only be used by professional installers, as incorrect entries can disable the entire keypad function.

0 0 0 0

4 1

Wrong Code Lockout

Option

# of tries

5 to 10

Confirm

Function
After 10 successive wrong codes, 30-second lockout
After 5 to 10 wrong codes, 15-min. lockout - Can reset wi h Master Code
None of the above

#

#

7 0

7 2

7 6 0 0

Door Unlocked Announcer

Option Code entry

Confirm

Function

1-sec. beep notifies the user to open the door when the output relay is ac ivated.

The beep is disabled, replaced by 2 short beeps for valid user codes.

#

#

8 1

1

0

User Code Entry Mode

Op ion Code entry

Confirm

Function

Auto Entry Mode is selected. The key that follows he user code is NOT required in
code entry. The User Codes MUST be set to the same digit length as the Master Code.
Manual Entry Mode is selected. The key that follows the user code is required in
code entry. The User Codes can be 4-8 digits, but not necessarily all of the same length.

#

#

8 2

1

0

#

#

Keypress Beeps

Op ion Code entry

Confirm

Function

Keypad beeps when a key is pressed.

Silent operation -- keypad does not beep when a key is pressed.

#

#

8 3

1

0

Exit Programming Mode

Confirm

Function

Exits programming mode, returns keypad to normal operations

*

(DEFAULT: Momentary, 1-sec. output)

(DEFAULT: 10 tries / 30 seconds)

(DEFAULT: On)

{

{

(DEFAULT: Manual)

(DEFAULT: On)

Relay Output Inhibit Control (lockout mode)

Option Code Entry

1 to 999

Confirm

Function

Lockout for 1 to 999 seconds
Lockout shunt mode (ON/OFF)

#

#

5 0

5 1

(DEFAULT: Momentary, 1-sec. output)

To print out a blank worksheet where all user codes
can be recorded, please visit www.seco-larm.com
and select the Model #, "SK-1011-SQ" in the drop
down menu for the burglar section. On the product
page click on "User Code Worksheet," which will
load the .PDF.

{

LED Flashes in Standby Mode

Code entry

Confirm

Function

Amber LED ON during standby mode.
Amber LED OFF during standby mode.

{

(DEFAULT: On)

Page 3

Page 6