The maximum current value is changed to 14A (for C3082) or 17A (for C3682) to prevent power breaker

tripping. (It is set to 24A when the unit is delivered from the factory.)

<Maximum Current Value Change Procedure>
(1) Remove the inspection panel.

Refer to Fig. 2 in " Noise Reducing Control" for details.

(2) When the switch No.2 of the dip switch (SW01) on the control P.C.Board is turned ON,

the maximum current value change. (Fig. 4)

Maximum Current Value Change Function

< C3082 >

Current Value on

the Point C

Current Value

on the Point B

Current Value

on the Point A

In cooling

operation

< C3682 >

Current Value on

the Point C

Current Value

on the Point B

Current Value

on the Point A

(25.0)

22.0

21.6

(25.0)

24.0

23.6

In cooling

operation

Dip Switch (SW01)

Switch No.2

ON

OFF

Max. Current Value

C3082

C3682

14.0A

17.0A

22.0A

24.0A

1. When the high load is given (Outside temperature is high in the cooling operation),

the capacity is reduced.

When the maximum current value change function is to be enabled, make sure to receive

the approval of the client.

2. The maximum capacity for cooling operation is about as much as the rated capacity.

NOTE

Description of function

Example of operation

Frequency

Frequency

Current

Stops operation

Approx.3 minutes

Power Point C

Point B

Point A

Target

frequency

Operates at the target frequency at Point A and below.

Stops increases to the frequency between Points A and B.

Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.

Stops operation, and restarts it appoximately 5 minutes later, if Point C is

exceeded.

(May operate when sudden voltage fluctuations occur. Indicates trouble.)