System Sensor TEMPORAL TONE SOUNDER BASE B501BHT User Manual

Page 3

Advertising
background image

D550-06-00

3

I56-1367-004R

Figure 4. Wiring diagram:
Detector Activates Sounder Base(s) - (Complies with UL268)
UL has approved grouping for up to six B501BHT base with
horn units. When wired as a group, any detector in the group
that has its LED’s latched on by the panel will cause other
B501BHT units in the group to sound. This type of “local”
grouping is accomplished by wiring the grouped devices to-

INTELLIGENT

MONITOR

MODULE

(+) 2

(–) 1

6

7

U.L.

LISTED

EOL

RESISTOR

47K

U.L.

LISTED

EOL

RELAY

24V

5

4

1

2

3

5

4

1

2

3

5

4

1

2

3

(+) COMM.

(–) COMM.

(–) POWER

(+) POWER

U.L. LISTED COMP

A

T

IBLE

CONTROL

P

ANEL

EXTERNA

L

24V SUPPL

Y

CLASS A OPTIONAL WIRING

CLASS A OPTIONAL WIRING

*

GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.

OPTIONAL SOUNDER INTERCONNECT

*

gether using terminal 5, Sounder Base Interconnect, as shown
in the diagram.
NOTE: Since a local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation system.
It is not acceptable to group horns for primary alarm signaling.

C0474-00

UL LISTED

COMPATIBLE

CONTROL

PANEL

INTELLIGENT

MONITOR

MODULE

INTELLIGENT

RELAY

MODULE

FIRST

SOUNDER

BASE

(+) POWER

(–) POWER

LAST

SOUNDER

BASE

(–) COMM.

(+) COMM.

UL

LISTED

EOL

RELAY

24V

UL LISTED

EOL

RESISTOR

47k

UL LISTED

24V SUPPLY

SLC

(+)

(–)

THIS IS A STANDARD RELAY

MODULE CONFIGURED TO

REVERSE THE POWER

OPTIONAL SOUNDER INTERCONNECT

*

*

GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.

Figure 5. Wiring diagram:
Detector Activates Sounder Base(s); Intelligent Relay Module Ac-
tivates All Sounder Bases - (Complies with UL 268 and UL 464)
UL has approved grouping of up to six B501BHT bases with
horn units. When wired as a group, any detector in the group
that has its LED’s latched on by the panel will cause other
B501BHT units in the group to sound. This type of “local”

C0968-00

grouping is accomplished by wiring the grouped devices to-
gether using terminal 5, Sounder Base Interconnect, as shown
in the diagram.
NOTE: Since a local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation sys-
tem. It is not acceptable to group horns for primary alarm
signaling.