Connecting to the network, Network connector, Network terminator jumper – Schneider Electric 170 LNT 710 00 User Manual
Page 8
DeviceNet Communication Adapter
6
1.4
Connecting to the Network
1.4.1
Network Connector
The adapter has one 5–pin male connector for connection to the network. Its
pin–to–pin spacing is 5.00 mm. A suggested mating connector is: Schneider
Automation part 170 XTS 060 00.
Figure 3
Network Connector
Front Panel
Pin
Connection
1
V–
2
CAN_L
3
Shield
4
CAN_H
5
V+
Top View
1
2
3
4
5
Wire Color
Black
Blue
– –
White
Red
1.4.2
Network Terminator Jumper
The adapter has a jumper to provide terminating impedance to the network cable.
It is shipped with the jumper in the non–terminated position (pins 3 and 4). If the
adapter is being installed as the last node on the network cable, move the jumper
to pins 1 and 2 and mark a “X” in the box provided on the adapter’s bottom panel.
Figure 4
Network Terminator Jumper
Rear View
1/2
IN
3/4
OUT
OUT
IN
The adapter is
shipped with
the Jumper on
pins 3/4.
TERMINATED
If the adapter is the last node on the
network cable, move the Jumper to
pins 1/2, and mark an ’X’ in the
TERMINATED box on the Bottom Panel.
X
Circuit Board
Pin
Termination
Bottom Panel View