Pulse output module diagnostic led’s, Specifications – Siemens IGWIPS200-1 User Manual

Page 33

Advertising
background image

IGWiPS200-1

PULSE OUTPUT MODULE DIAGNOSTIC LED’S
There are 3 diagnostic LED’s on the pulse output module:

Status LED: On solid when I/O is functional and flashing if there is a conflict with another module.

Pulse Input 1 and 2 LEDs: These lights will flicker at a varying frequency depending on the frequency of
pulses being generated:

Frequency Range (Hz)

LED Flashing Frequency (Hz)

1 ≤ frequency ≤ 10

1

10 < frequency ≤ 100

4

100 < frequency ≤ 1000

8

1000 < frequency ≤ 32K

On solid

SPECIFICATIONS

Transceiver
Frequency .............................................................902 to 928 MHz industrial, scientific, and medical (ISM) band
Technology...........................................................Frequency Hopping Spread Spectrum
Power Input ..........................................................9-30 Vdc; reverse polarity and surge protected
Power Consumption .............................................75 mA (average), 200 mA (peak) @ 24 Vdc during transmission

(plus I/O modules), 5A (maximum)

Inputs

Analog ...........................................................1, 4 to 20 mA (16-bit, 125 Ohms impedance

Digital............................................................2, 5 to 36 Vac/Vdc (for 120 Vac digital inputs use relays to convert

to specified voltage levels; consult factory for relay options)

Outputs

Analog ...........................................................1, 4 to 20 mA, 12-bit resolution, short circuit protected

Digital............................................................2,

250 Vac / 30 Vdc, 2A dry contact

RF

Link .........................................................1, 250 Vac / 30 Vdc, 2A dry contact

Repeatability (4-20 mA Current Loop) ................0.02%
Accuracy (4-20 mA Current Loop) ......................0.2% full scale
Transmitter Power Output ....................................1 Watt (30 dBm)
Range

Standard Omnidirectional Antenna ...............600 to 1000 feet (183m to 305m) in-plant, obstructed LOS

6

Optional Omnidirectional Antenna ...............4 to 5 miles (6.5 km to 8 km) clear LOS, flat terrain, raised antenna

Optional Yagi Antenna..................................15 to 20 miles (24 km to 32 km) clear LOS, flat terrain,

professional propagation study and installation

Antenna Connector ...............................................MCX female, 50 Ohms
Operating Temperature Range..............................-40°C to 70°C (-40°F to 158°F)
Humidity...............................................................20% to 90% non-condensing
Dimensions ...........................................................4.5" x 3.9" x 0.9" (114 mm x 99 mm x23 mm)
Faceplate Label Color...........................................White
Weight ..................................................................5.3 oz (150g)
Environmental ......................................................NEMA 1, equivalent to IP 20
Approvals
USA...............................................................FCC

47CFR15.247

Canada...........................................................ISC RSS 210

UL and CUL..................................................Class I, Div. 2, Groups A, B, C, D; Temp. Code T5

CSA ...............................................................Approved

6

LOS – Line of Sight between transmitting and receiving antennas

May 2007

31

Advertising