State GPG/GPV-540A User Manual

Page 24

Advertising
background image

24

1. Check gas line pressure with a manometer.

Set initial gas line pressure at 9-10” w.c. before turning the

heater “ON”.

Read gas line pressure and gas manifold pressure when the

heater main gas is “ON”.

Adjust gas line regulator setting if the gas line pressure drops

below 8” w.c. when heater main gas is “ON”.

Check heater gas manifold pressure (see Table 10) using a

manometer connected to the manifold pressure tap on the

Robertshaw gas control valve, see Figure 10.

important Note: Use gas manifold pressure as initial setup

only. The final air and gas settings should be based on fire

rate and flue gas 0

2

/C0

2

reading, see Table 10 for normal 0

2

/

C0

2

reading.

wArNiNG

Excessive gas line pressure drop and/or burner manifold

pressure too low may cause burner start/operate with

excessive noise!

2. Cycle the burner “ON” and “OFF” several times to check

its operation. Make sure the gas line pressure is below

14” w.c. when burner is “OFF”. If gas line pressure exceeds

14” w.c. when the burner is off, the gas supply line size

must be increased to correct this problem (see Table 9 for

gas pipe size).

3. Check the operation of the limiting and operating controls.

4. Check the vent system seams and joints and ensure that there

is no discharge of flue products into the room. For standard

vertical vent systems, check the barometric damper control to

make sure it operates freely and there is no discharge of flue

products into the room.

5. Check the input rate by clocking the gas meter.

ADJUSTMENT PrOCEDUrE FOr FirE-rATE,

LOw NOX AND HiGH ELEVATiON (Fine-Tune)

An acceptable input rate is within 2% of the rated input for the

model. Should it be necessary to adjust the gas pressure to the

burner and/or air damper of the blower to obtain the full input rate,

these steps should be followed:

wArNiNG

Never set burner combustion too lean (causing noisy

operation) or too rich (causing combustion chamber

premature failure) see Table 10 for proper settings.

wArNiNG

Never set air damper outside of its adjustment range of the

rated fire rate unless authorized by a state service center.

important Note: Final gas and air settings should be based on flue

gas CO

2

or O

2

reading (see Table 10). Increase burner manifold

pressure will increase fire rate and flue gas CO

2

reading. Increase

air damper setting will decrease fire rate and decrease flue

gas CO

2

reading. Adjustable air damper is preset for the rated

fire-rate prior to delivery, should not be re-adjusted unless it’s

a high elevation application and/or a direct vent (long air intake

vent) application.

1. Fire Rate Adjustment (including direct vent installation).

a.

Make sure the gas supply line pressure reads

8” w.c. (2 kPa) or higher when the heater is running.

b.

Remove the pressure regulator cover screw

(Figure 10) and adjust the pressure by tuning the

adjustment screw w/a small screwdriver clockwise to

increase gas pressure into the burner and fire rate.

Counterclockwise to decrease gas pressure and input

rate.

c.

Clock gas meter, repeat above Step (b) to achieve the

specific input rate.

d.

Measure flue gas O

2

and/or CO

2

(see Table 10) for

acceptable O

2

/CO

2

range.

If the O

2

or CO

2

reading is within the acceptable range,

then proceed to Step (f).

If the O

2

or CO

2

reading is out of range, adjust air

damper is required.

e.

Repeat Steps (b), (c), (d) if air damper is adjusted.

f.

Cycle heater ON/OFF.

g.

Replace the gas regulator cover, pressure tap and

tighten the damper center bolt.

2. Adjustment for Low NOx Emission Application.

The water heater is preset at factory for Low Nox emission

combustion. Due to the installation variations, fine-tune

adjustments may be required. To lower NOx emission level

(30PPM corrected at 3% O

2

or lower is required by SCAQMD),

air damper setting may need to be slightly increased. To

increase air damper setting, loosen the center nut of the

inlet air damper, rotate the damper clockwise slightly, then

tighten the center nut. After re-set the air damper, cycle heater

ON/OFF and check fire-rate and flue gas CO

2

/O

2

reading.

3. Adjustment for High Elevation Application

Installation above 2000 feet sea level require new air damper

settings. All the final settings should be based on flue gas

CO

2

/O

2

reading, see Table 10. To increase air damper setting,

loosen the center bolt of the inlet air damper, rotate the damper

clockwise slightly, then tighten the center bolt. After re-setting

the air damper, cycle heater ON/OFF and check fire-rate and

flue gas CO

2

/O

2

reading.

wArNiNG

UNDEr NO CirCUMSTANCES SHOULD THE iNPUT rATE

EXCEED THE iNPUT rATE SHOwN iN THE HEATEr rATiNG

PLATE. OVErFiriNG COULD rESULT iN DAMAGE Or

SOOTiNG OF THE HEATEr.

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL

TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE

TO THE APPLIANCE.