Slant/Fin Caravan LZDF series User Manual

Modular boiler submittal data, Lzdf series, Dual fuel/steam

Advertising
background image

Modular Boiler Submittal Data

LZDF SERIES—

Dual Fuel/Steam

A Caravan modular boiler system con-
sists of two or more compact boilers that
offer significant advantages in terms of
installed cost, efficiency and reliability.
Caravan systems are based on step-firing
just enough modules to meet heating
demands. LZDF systems are available in
620,000 to multi-million Btuh gross input.
For additional information, see Caravan
Engineering Manual, pub. C-30.

Standard Equipment

One per module unless otherwise noted
Pre-assembled heat exchanger with

insulated jacket.

Dual fuel gas/oil burner with oil valve, gas

regulator, gas valve, flame safeguard
with UV scanner and on-off fuel transfer
switch (unmounted). Gordon-Piatt burner
model #S4.1-GO has intermittent gas
pilot to light oil and/or gas main flame.

Module pressure gauge and siphon

(unmounted).

System pressure gauge and siphon

(unmounted, one per system).

*

Light oil, 140,000 Btu per gallon.

‡ Based on 150 Btuh per square foot E.D.R. at 170°F average water temperature.

Net ratings are based on piping and pick-up allowance of 1.33. Slant/Fin
should be consulted before selecting a boiler for installation having unusual

§ Modules in excess of 8 are piped in parallel in two or more banks.

piping and/or pick-up requirements. For higher elevations, input may need to
be reduced.

LZDF-600-2-5

2

620

500

83.30

375

1563

14.9

4.30

602

500

85.90

375

1563

14.9

21.4 1506

3"

LZDF-750-2-6

2

750

592

83.20

444

1850

17.7

5.20

728

592

85.80

444

1850

17.7

25.2 1710

3"

LZDF-850-2-7

2

798

620

82.90

466

1946

18.6

6.00

840

674

85.50

506

2108

20.1

29.0 1918

3"

LZDF-900-3-5

3

930

750

83.30

563

2346

22.4

6.40

896

750

85.90

563

2346

22.4

32.1 2259

3"

LZDF-1100-3-6

3

1125

888

83.20

666

2775

26.5

7.80 1092

888

85.80

666

2775

26.5

37.8 2565

5"

LZDF-1300-3-7

3

1197

930

82.90

699

2917

27.9

9.00 1260 1011

85.50

758

3158

30.2

43.5 2876

5"

LZDF-1700-4-7

4

1596

1240

82.90

932

3888

37.2 12.00 1680 1348

85.50 1018

4242

40.3

58.0 3834

6"

LZDF-2100-5-7

5

1995

1550

82.90 1165

4963

46.5 15.00 2100 1685

85.50 1298

5408

50.3

72.5 4794

6"

Module pressure re-

lief valve, ASME
(unmounted) 15 psi.

Double swing draft

regulator (unmounted).

Flue brush.
Drain cock (unmounted).
Water level sight glass

(unmounted).

Standard Equipment

Dual fuel changeover thermostat.
Internal tankless heaters.
Two-stage fuel pump in place of one-
stage fuel pump.
ASME Package—includes:
67 Low water cutoff (one per module)
PA404A Pressure control (one per mod.)
67M Low water cutoff (one per system)
L4079B Manual reset pressure

Ratings

Model No.

No.

of

Htg.

Mods

Input

MPH

Gross

Output

MPH

Comb.

Efficiency

Net

Output

MPH

Sq. Ft.

Steam

Horse-

power

Firing

Rate

GPH*

Input

MPH

Gross

Output

MPH

Comb.

Efficiency

Net

Output

MPH

Sq. Ft.

Steam

Horse-

power

Boiler
Water

Content

(gal)

Weight

with

Water

Recom-

mended

Header

Size

I=B=R

RATINGS FOR GAS

RATINGS FOR OIL

I=B=R

Dual Fuel Caravan ratings and dimensions/steam models–LZDF Series

®

Advertising