When the use of industrial antifreeze solutions is not possible, the system
must be operated to meet both of the following conditions.

1. Maintain sufficient flow rate through the coil.

2. Maintain sufficient heat load on the process fluid. Fluid exiting the

coil must be maintained at or above 7°C. Cycling of the recirculation
pump should not be used to control process temperatures.

Draining the coil is not acceptable as a normal method of freeze
protection—draining promotes corrosion inside the coil tubes. Drain-
ing is acceptable in an emergency if the coil is not protected by an
antifreeze solution.

It is recommended that you discuss your freeze prevention options with
your local Marley sales representative.

Operation

Note

Model

Coil Volume

Liters

Model

Coil Volume

Liters

MHF702__061

246

MHF705__061

890

MHF702__081

322

MHF705__081

1192

MHF702__101

397

MHF705__101

1476

MHF702__121

473

MHF705__121

1760

MHF702__062

284

MHF705__062

1079

MHF702__082

379

MHF705__082

1438

MHF702__102

454

MHF705__102

1779

MHF702__122

568

MHF705__122

2139

MHF703__061

322

MHF706__061

1476

MHF703__081

435

MHF706__081

1893

MHF703__101

530

MHF706__101

2309

MHF703__121

644

MHF706__121

2744

MHF703__062

379

MHF706__062

1798

MHF703__082

492

MHF706__082

2309

MHF703__102

625

MHF706__102

2839

MHF703__122

757

MHF706__122

3350

MHF704__061

606

MHF707__061

1703

MHF704__081

795

MHF707__081

2196

MHF704__101

984

MHF707__101

2688

MHF704__121

1173

MHF707__121

3180

MHF704__062

719

MHF707__062

2158

MHF704__082

946

MHF707__082

2801

MHF704__102

1192

MHF707__102

3426

MHF704__122

1420

MHF707__122

4054

Advertising
This manual is related to the following products: