Gt installation and operation instructions page 14 – Smith Cast Iron Boilers GT Series User Manual

Page 14

Advertising
background image

GT INSTALLATION AND OPERATION INSTRUCTIONS

Page 14

Air Vent

Union Automatic

Thermometer

Pressure

Relief Valve

Reducing

Check Valve

Pressure

Pump

Ball Valve

Gate Valve

Backflow-Prevention

Device

Drain Valve

(Typ.)

Heating

Load

Valve

Differential Pressure

Bypass Valve

Spirotrap

Fine Particulate

Separator

Figure 23 - Single Boiler with Indirect Hot Water Heater

NOTES:
1.

All piping and pumps must be supported so that no loads or stresses are applied to boiler heat exchanger. To make boiler service easy
use Unions or fl exible Vibration Isolation Kit.

2.

This boiler is provided with a 1/8" vent that is not intended for continuous system venting.

3.

For continuous system venting use a cast iron air scoop, for excessive air conditions use a Spirovent. Do not fi re boiler until all air is
purged from the system piping. Heat exchanger damage caused by air is not covered by warranty.

4.

See Table 3 for boiler pump fl ow requirements. This pump is wired to terminals C1-L2.

5.

See Table 3 for Indirect Water Heater pump fl ow requirements. This pump is wired to terminals AP-L2.

6.

Set pressure reducing valve to 12 PSI.

7.

Use 30 psi relief valve max. Locate where discharge will not cause injury or damage. Follow local codes.

8. Add an inhibitor to protect system. (CHP from Fernox)
9.

Boiler circuit piping must be sized large enough to handle maximum fl ow through unit.

10. Suggested piping. When installing an indirect water heater consult manufacturer’s manual for full details.
11. Do not install any valves between the Vacuum Relief valve and the tank.
12. Do not operate boiler with service valves closed isolating the boiler from the expansion tank.
13. Failure to follow these instructions will result in heat exchanger damage: All fl ux and contaminants must be fl ushed from piping before

connecting boiler. Do not connect this boiler to older systems with cast iron radiation without installing a fi ne particulate separator. TYP:
Spirotrap Junior Model TDN 125 FT. Do Not use non-oxygen barrier radiant tubing.

Notice: This drawings show suggested piping confi guration and valving. Check with local codes and ordinances for specifi c requirements.