* “W” = Total width of the fluid cooler.

unit. If these requirements are not met, unit must be installed
as indicated for “Units in pits”.

Fences must have 50% free area, with 1 foot undercut,

a “W” minimum clearance, and must not exceed the top of

Decorative Fences

If the top of the unit is not level with the top of pit, dis-

charge cones or stacks must be used to raise discharge air to
the top of the pit. This is a minimum requirement.

The top of the unit should be level with the top of the pit,

and side distance increased to “2W”.

Units in Pits

For units placed side by side, the minimum distance

between units is the width of the largest unit. If units are placed
end to end, the minimum distance between units is 4 feet.

Multiple Units

room is left for maintenance work through access doors and
panels. Overhead obstructions are not permitted. When the
unit is in an area where it is enclosed by three walls the unit
must be installed as indicated for units in a pit.

The unit should be located so that air may circulate freely

and not be recirculated. For proper air flow and access all
sides of the unit should be a minimum of “W” away from any
wall or obstruction. It is preferred that this distance be increased
whenever possible. Care should be taken to see that ample

Walls or Obstructions