Maintenance – SPX Cooling Technologies MARLEY CLASS F400 User Manual

Page 11

Advertising
background image

11

Spare Parts

SPX Cooling Technologies manufactures and maintains a stock of replacement
parts for the mechanical equipment. Shipment of these parts are normally made
within ten days after an order is received. If emergency service is necessary,
contact the local Marley representative for assistance.

To prevent prolonged shutdown periods in case of damage to the mechanical
equipment, it is suggested that the following parts be carried in the owner’s
stock:

• One fan assembly.
• One Geareducer assembly.
• One driveshaft assembly.

Be sure to furnish the tower serial number when ordering parts.

Seasonal Shutdown Instructions

Tower

–Drain all tower piping.

During shutdown, clean the tower and make any necessary repairs. Apply
protective coating as required to all metal parts. Particular attention should be
given to mechanical equipment supports, drive shaft and drive shaft guards.

Mechanical Equipment

Geareducer (shutdown for 3 months or less).

1. Each month, drain water condensate from the lowest point of the Geareducer

and its oil system. Check oil level and add oil if necessary. Operate to recoat
all interior surfaces with oil.

2. At start-up, drain water condensate and check oil level. Add oil if neces-

sary.

Refer to the Geareducer User Manual for maintenance and lubrication
instructions.

maintenance