Sea-Fire FM200 User Manual

Page 2

Advertising
background image

WARNING

CONCENTRATED AGENT AND BY-PRODUCT OF APPLICATION TO FIRE ARE TOXIC.
AVOID BREATHING OF FUMES OR PROLONGED EXPOSURE. ACCIDENTAL DIS-
CHARGE MAY OCCUR DURING HANDLING OR INSTALLATION OF THIS DEVICE, READ
AND COMPLY WITH INSTRUCTIONS, WARNINGS, AND LIMITATIONS CONTAINED IN
THIS MANUAL. DO NOT LIFT, CARRY, OR HANDLE BY VALVE. DO NOT DROP. KEEP
AWAY FROM HEAT. KEEP AWAY FROM CHILDREN.

APPLICATION

FM-200

®

(CF3CHFCF3), the extinguishing agent, used in all Sea-Fire “FT’’ series fire extin-

guishers, is a suitable EPA accepted alternate replacement for Halon. FM-200

®

is electrically

nonconductive and residue free extinguishing agent that requires no cleanup.

These features and the versatility of design make the “FT’’ series fire extinguisher ideal for a
broad range of applications. The systems are ideal for small volumes, 150 cubic feet or less,
that are difficult to access. These applications would include marine, recreational vehicles,
commercial and industrial use where flammable liquids are likely source of fire.

Application Examples:
• Engine Compartments (maximum 150 cubic feet)
• Bow Thrusters
• Small Generator Set Enclosures
• Consoles
• Electrical Enclosures
• Flammable Liquid Storage Areas
• Pump Enclosures
• Alternative Fuel Storage Areas

Sea-Fire “FT” extinguishers are designed to induce a minimum atmospheric concentration of
10.0% within the protected compartment.* The specification table in this manual lists the
minimum and maximum approved compartment volume (size) allowable for each model.
Volume can be determined by multiplying the compartment’s length x width x height which
equals the volume in cubic feet or meters (LxWxH=V).

Exception: If the boat manufacturer has placed a permanently affixed label in the compart-
ment specifying the gross volume less the volume of permanently installed tankage, then
this volume may be used to determine the proper size extinguisher. Check specification table
for proper application before making installation.

*Reference: NFPA-2001 National Fire Protection Assoc. Boston, MA and UL 2166

Underwriters laboratories

SEA-FIRE “FT” SERIES AUTOMATIC FIRE SUPPRESSION SYSTEMS

FT — STINGER SPECIFICATION TABLE

AREA OF

FM-200 @

DIAMETER X

MODEL

PROTECTION

240 PSI

HEIGHT

TUBE PART # / LENGTH

CU.FT.

CU.M.

AUTO

AREA

AREA

LBS.

KG

INCH

MM

PART#

FT.

MM

FT-25

25

0.7

1.25

0.56

3.0 X 11.2

76 X 285

130-121

10

3000

FT-50

50

1.4

2.50

1.13

3.1 X 13.5

78 X 342

130-121

10

3000

FT-75

75

2.1

3.75

1.70

3.1 X 16.5

78 X 419

130-121

10

3000

FT-100

100

2.8

5.00

2.26

3.5 X 17.5

89 X 444

130-122

15

4500

FT-125

125

3.5

6.25

2.83

4.1 X 17.0 104 X 432

130-122

15

4500

FT-150

150

4.2

7.50

3.40

5.2 X 19.0 132 X 482

130-122

15

4500

CU. FT. = Cubic Feet

FT. = Feet

KG = Kilograms

CU.M. = Cubic Meters

LBS. = Pounds

MM = Millimeters

CAUTION: NEVER INSTALL A UNIT WITH A VOLUME RATING LESS THAN THE GROSS
VOLUME OF THE COMPARTMENT TO BE PROTECTED. DO NOT DEDUCT FOR
ENGINES, REMOVABLE TANKS OR OTHER EQUIPMENT.

2

Advertising