Recold, Jt series, Accessories – SPX Cooling Technologies Recold JT Series User Manual

Page 4: Cooling tower

Advertising
background image

Recold

/

JT Series

Cooling Tower

/

Accessories

4

CAPACITY CONTROLS

Dual Fan Motors—The dual fan motor package is available

as a proven energy saving capacity control option. It

consists of furnishing a high efficiency motor, a 1200 RPM,

low speed motor, two sets of drives and belts, extended

fan shaft and motor bases on opposite sides of the blower.

A UL control-starter panel is available as a completely wired

package for one point connection.
Variable Speed Drive—A Variable Speed Drive

automatically minimize the tower’s noise level during

periods of reduced load and/or reduced ambient

temperature without sacrificing the system’s ability to

maintain a constant cold water temperature. This is a

relatively inexpensive solution, and can pay for itself quickly

in reduced energy costs.
Electric Damper Controls—An electric damper control

package is available as an accessory for modulating the

internal damper system. A proportional solid state actuator

is factory mounted below the fan scroll and attached to

the damper shaft by connecting linkage. A sensing bulb

connected to the actuator by a capillary tube is normally

mounted in the unit pan water basin for monitoring the

system. However, when specified, a pressure control may

be supplied for field mounting to allow direct head pressure

control. An end switch located inside the motor actuator

may be adjusted to cycle the fan motor on for pressure rise

and off when dampers close.

CASING INSULATION

In order to further reduce the heat loss from the unit

coil, factory installed insulation on exterior coil panels

is available. A protective coat of paint is applied to the

insulation for protection from the weather elements.

CONTROL – STARTER PANEL

Contains the fan motor starter, disconnect switch,

thermostat sensing the cold water temperature to control

the fan motor and control transformer when required by the

supply power characteristics. All components are contained

in a NEMA 12 enclosure with UL label and mounted on the

unit. Fan motor and controls are factory wired to the panel

to provide single point connection for users power supply.
Panels for dual fan-motor arrangement include elapsed

time meters for both motors to aid in determining energy

savings. NEMA 3R and 4 enclosures are also available.

VIBRATION ISOLATORS

Spring type vibration isolator rails may be supplied for field

installation—some units will require base frame structural

support.

ELECTRONIC WATER LEVEL CONTROL

The electronic water level control package provides a

constant and accurate means of monitoring water level in

the unit. For this reason, it is often recommended for those

installations which require year round operation in low

ambient conditions.
The complete package includes an electric float switch with

stilling chamber which is factory installed in the pan section

of the unit. An electric solenoid valve for water make-up

is shipped loose for remote installation. All wiring must be

provided in the field by others.

PAN HEATER

The use of a remote sump tank located indoors is

a common form of pan water freeze protection for

evaporative cooling equipment. However, for those

installations which will not allow this type of system, freeze

protection may be provided by electric immersion heaters or

steam or hot water coils installed in the pan.
The electric heater package consists of immersion

heaters installed in the pan to provide efficient even

heat distribution. Standard heaters are selected to

provide approximately 40°F pan water at -10°F ambient

temperature. A low water cutout switch is supplied to

prevent heater operation when the elements are not

completely submerged. The heaters are monitored by a

sump thermostat with remote sensing bulb located in the

pan water. All heaters and controls are factory installed for

field wiring by others.
NOTE: Pan heater packages are designed to prevent

pan water freezing during unit shutdown with fans and

pump idle.

STAINLESS STEEL CONSTRUCTION

In addition to the standard stainless steel basin, fill supports

and access doors, 300 stainless steel construction is

offered as an option for upper casing panels.

RECOLD PRODUCTS
550 W MERCURY LANE
BREA, CALIFORNIA 92821
UNITED STATES
704 529 6080
[email protected]

spxcooling.com

In the interest of technological progress,
all products are subject to design and/or
material change without notice.
©2008 SPX Cooling Technologies, Inc.
Printed in USA | RECOLD JT-TECH-07A