Specifications, Gas sensor monitors – Sierra Monitor Corporation Hydrogen Sulfide 2003 User Manual

Page 2

Advertising
background image

Rev. A2-4-15-11 © 2008 by Sierra Monitor Corporation

Model 2001 Combustibles Gas Monitor

The Model 2001 can detect a wide range of combus-
tibles. Typical applications include combustible gas
monitoring in basements near waste dumps, manhole,
tanks, parking garages and vehicle maintenance facili-
ties, laboratories, chemical plants, and more.

OUTPUT:

0.5 AMP dry contact. 100 VDC, 130 VAC
Nominal 5 volts DC, source 25 mA, SAFE and
ALARM signals 70 dB buzer.
TTL interface to Model 2102 Alarm Panel is
user configurable.

RESPONSE TIME:
Model 2001

Less than 30 seconds

Model 2003

Less than 60 seconds

Model 2006

Less than 30 seconds

PERIODIC
MAINTENANCE:

None, other than routine calibration

OPERATING

TEMPERATURE

-4

o

F to158

o

F

RANGE:

-20°C to 70°C

ENCLOSURE
MATERIAL:

Aluminum

SIZE:

3.7 x 2.2 x 1.1 in. (9.4 x 5.7 x 2.8 cm)

WEIGHT:

3.8 oz (108 g)

APPROVAL:

UL 61010-1:2001

CSA-C22.2

Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-6611 800-727-4377 FAX: (408) 262-9042

Visit our Web site at: www.sierramonitor.com E-Mail: [email protected]

Model 2006 Carbon Monoxide Monitor

The Model 2006 Carbon Monoxide Gas Sensor Mod-
ule can be used to provide an early warning of CO
accumulation in tanks, laboratories, chemical plants,
parking garages, vehicle test facilities and more.

ORDERING INFORMATION

Combustible Gas

2001-00

Hydrogen Sulfide

2003-00

Carbon Monoxide

2006-00

Model 2003 Hydrogen Sulfide Monitor

The Model 2003 can be used in such typical applica-
tions as waste water treatment plants, laboratories and
chemical plants.

SPECIFICATIONS

INDICATORS:
Visual:

Green LED for Monitor “ON"/Safe
Red LED for Alarm
LEDs oscillate on/off for sensor failure

Audible:

Sustained alarm tone for as long
as gas is present. Interrupted tone or sensor
failure.

SENSOR TYPE:

Solid-State Metal Oxide Semiconductor

RANGE;

(at 50% relative humidity)

Model 2001

300-2,000 ppm Hydrogen
500-10,000 ppm Methane

Model 2003

10-50 ppm Hydrogen Sulfide (H

2

S)

Model 2006

50-500 ppm Carbon Monoxide (CO)

FACTORY ALARM
SETPOINT:
Model 2001

1000 ppm Methane

Model 2003

50 ppm H

2

S

Model 2006

100 ppm CO

INPUT:

9 - 24VDC (+1V), 250 mA
Plug-in 120 VAC AC/DC Power Supply is

provided