Sentric np fuse switch disconnectors, General data – Siemens AC-21A User Manual

Page 19

Advertising
background image

Siemens LV 10 · 2004

7/19

SENTRIC NP Fuse Switch Disconnectors

General data

7

1) Only for isolating links; otherwise note instructions of the fuse manufac-

turer.

Standards

IEC 60 947-1, IEC 60 947-3, VDE 0660 Part 107

Type

3NP40 1

3NP40 7

3NP42 7

3NP43 7

3NP44 7

Capacitor switching capacity

at AC 400 V
Capacitor power

kvar

50

50

Rated current I

n

A

72

72

at AC 525 V
Capacitor power

kvar

50

50

Rated current I

n

A

55

55

Permissible ambient temperature

°C

–25 ... +55

1)

for operation, –50 ... +80 for storage

Mechanical endurance

Operations

2000

2000

1600

1000

1000

Degree of protection
(with respect to the operator side)

Without molded-plastic masking frame/cable
lug cover

IP00 (3NP40 with box terminal and properly connected conductors: IP20)

With molded-plastic blanking plate/cable lug
cover

IP30 (contacts closed), IP20 (contacts open)

Power loss of the switch disconnector at I

th

(plus power loss of the fuse links)

a

Without busbar adapter

W

4.5 (at 100 A)

10

15

30

47

With busbar adapter

W

8.5 (at 100 A)

20

47

83

127

Main conductor connection

Flat pad connection for cable lug,
max. conductor cross-section (stranded)

mm

2

up to 2 × 70
(M 8)

up to 150
(M 10)

up to 240
(M 10)

up to 2 × 240
(M 12)

Box terminal/supply terminal
(finely stranded with end sleeve)

mm

2

1.5 ... 50 (35)

2.5 ... 70 (50)

70 ... 150

120 ... 240

150 ... 300

Conductor bar (width x thickness)

mm

22 Ч 5

22–30 Ч 5–10

22–30 Ч 5–10

25–40 Ч 5–10

Louvered Cu strips, unperforated in terminals
(width × thickness)

mm

8 × 8

up to 9 × 8

up to 16 × 8

up to 20 × 10

up to 24 × 10

Tightening torque for terminal screws

For flat pad connection

Nm

10 ... 12

25

25

30

With SIGUT box terminal/connection terminal

Nm

3 ... 3.5

8 ... 10

6

8

8

Auxiliary switch 1 CO (Accessory)

3NY3 035 AC 50 Hz/60 Hz up to 230 V
Rated operating current I

e

at AC-14

A

0.25 (I

th

= 5 A), at DC 24 V: I

e

= 0.45 A; flat connector to DIN 46244: A 2.8 × 0.5

3NY3 030 AC 50 Hz/60 Hz up to 230 V
Rated operating current I

e

at AC-13

A

0.1 (I

th

= 0.1 A); plug-in sleeve to DIN 46245: A 2.8 – 1

Permissible mounting position

Vertical or horizontal (no reduction in specified switching capacity)