Siemens 125-5033 User Manual

Page 26

Advertising
background image

Fume Hood Controller Owner’s Manual

18

Siemens Building Technologies, Inc.

Address Descriptor

Description

15

EMER STPT

A value of the preset FLOW STPT, in percent, that the controller uses as the
setpoint when EMER ALM is ON.

16

LOW WARN

This point displays an ON or OFF status. When the exhaust flow goes below the
value specified at LOW WARN LMT for the time specified in ALARM TIME, the
point goes into a warning state (ON); the yellow LED is illuminated at the ODP.

17

HIGH WARN

This point displays an ON or OFF status. When the exhaust flow goes above the
value specified at HI WARN LMT for the time specified in ALARM TIME, the
point goes into a warning state (ON), the yellow LED is illuminated at the ODP.

19

ALM AKNLG

This point displays an ON or OFF status that indicates the Horn Silence button
has been pressed at the ODP to acknowledge an alarm condition. The point will
reset when the alarm condition clears or another alarm is initiated.

27

AO2 DEADBAND

When EXH FLOW and FLOW STPT are different by more than the AO2
DEADBAND, the AO2 FLOW SIG changes from setpoint to actual flow.

30

AO2 RANGE

Scaling for the Analog Output (AO2) point. To get the correct output, the slope
and intercept of this point must match the point database of the room controller.

34

TRANS RANGE

The maximum range, in inches of water (PA), of the differential pressure
transmitter. Standard values are 0.1 (25.3), 0.25 (62.275), 0.5 (124.55), and 1.0
(253).

35

EXH FLOW

The calculated value, in CFM (LPS), of the exhaust airflow as measured with the
differential pressure transmitter sensor.

36

FLOW COEFF

Gain factor for the flow sensor.

37

FLOW STPT

Setpoint, in CFM (LPS), that the airflow is controlled to.

38

FLOW LO STPT

The low flow setpoint used in FLOW STPT.

40

CAL DP TRANS

YES or NO point used to calibrate the zero point of the differential pressure
transmitter.

41

DO1 SUP

Digital output 1 is used to control the analog output-pneumatic (AO-P) supply
valve or the AO-E module supply input.

42

DO2 EXH

Digital output 2 is used to control the analog output-pneumatic (AO-P) exhaust
valve or the AO-E module exhaust input.

43 DO3

Digital

output

3 is a spare output.

44

AI1 DP TRANS

Analog input 1, a 4 to 20 mA signal from the differential pressure transmitter.
The point displays the mA value of input from the sensor.

45

AI2 0.10V

Analog input 2 is a 0 to 10 Vdc spare input.

46

AO1 0.10V

Spare analog output is a 0 to 10 Vdc output.

47

AO2 FLOW SIG

Analog output 2 signal is used to indicate the exhaust flow setpoint. The output
is 1 to 10 Vdc, which corresponds to 0 to A02 RANGE (Point 30).

48

DI1 STPT SW

Digital input for dry contact connection to control the HI/LOW flow setpoint of the
controller.

54

ODP DISPLAY

Controls the function of the ODP display. It will display either CFM divided by
10 or HI FLOW / LO FLOW.

55

DO3 MODE

Controls the function of the DO3. It will follow either the HI/LO setpoint or the
alarm status.

Advertising