Electrical - general instructions – Strong Pools and Spas The Cyprus User Manual

Page 6

Advertising
background image

4

Connections should be made using copper conductors only. The connecting wire and circuit breakers
or fuses must be sized to accommodate the total ampere load as specified on the equipment module
data label.

Strong Pools and Spas only makes electrical recommendations, always consult a certified electrician.

It is recommended that a licensed electrician install the power to your spa, in accordance with
the National Electric Code or any local electrical codes in effect at the time of installation.

The circuit breaker must be dedicated and cannot be shared with any other appliances. It
should be labeled and easily accessible to users.

DO NOT USE EXTENSION OR PLUG-

TYPE CORDS OF ANY KIND.

The use of a shut-off box near the spa is recommended.

Metal surfaces within 5 feet of the spa must be grounded to the spa.

A 120 Volt - 20 Amp GFI rated plug is furnished with the Cyprus Spa.

CAUTION: This spa will not work if more than one GFCI is used on the circuit. On 220 Volt applications,

power supply must be hard wired into the power pack.

Electrical - General Instructions

110/220 Volt Cyprus

Electrical Connections:

220 Volt Cyprus

Electrical Connections:

Note: Your Cyprus Spa’s Heater can be converted to 220 Volts. The Spa’s pump will remain 120 Volts.

This change must be performed by a certified electrician.

To convert spa from 120 volt
to 220 Volt remove white
jumper wire from J11 and J32.

Next, move move dip switch
10 to the off position

Two Wire
& Ground

TERMINAL

BLOCK

Ground (copper or green)GRD

Live (black) Hot Black

Neutral (white) Neutral

Three Wire
& Ground

These wires go to
the PC Board
Control Circuit.

TERMINAL

BLOCK

Ground (copper or

green)GRD

Live (black) Hot

Neutral (white) N

Live (red) Hot

Hot Red