Architectural and engineering specifications, Technical specifications, Ordering information – Kidde Combination Smoke and Carbon Monoxide Alarm KN-COSM-B User Manual

Page 2

Advertising
background image

1394 South Third Street, Mebane NC 27302
1-800-880-6788 • www.kiddeus.com

Combination Carbon Monoxide
& Smoke Alarm

KN-COSM-B

Architectural and Engineering
Specifications

The combination smoke and carbon monoxide alarm shall be Kidde
Model Number KN-COSM-B (part number 900-0102) or approved equal.
It shall be powered by 3 AA batteries. The unit shall incorporate an
ionization smoke sensor with nominal sensitivity of 0.97 %/ft. The CO
sensor shall be of a fuel cell design and provide accuracy of +/-20% +
15ppm. The temperature operating range shall be between 40°F and
100°F (4°C and 38°C) and the humidity operating range shall be 5% -
95% related humidity.

The combination alarm can be installed on the surface of any wall or

ceiling following the UL/NFPA/Manufacturer’s recommended placement
guidelines. The alarm shall provide optional tamper resistance that deters
removal of the unit from the wall or ceiling.

The alarm shall include a test button that will electronically simulate

the presence of smoke and CO and cause the unit to go into both
modes of alarm. This sequence tests the unit’s electronics to ensure prop-
er operation.

The CO sensor will not alarm to levels of CO below 30 ppm and will

alarm in the following time range when exposed to the corresponding
levels of CO.

70 ppm CO Concentration 60 – 240 minutes
150 ppm CO Concentration 10 – 50 minutes
400 ppm CO Concentration 4 – 15 minutes

The combination alarm shall have two methods of warning for dan-

ger: a piezoelectric horn that is rated at 85 decibels at 10 feet and a
voice warning that identifies the danger. For a CO incident, the horn will
sound in the repetitive manner -- four (4) fast beeps, a short pause, four
(4) fast beeps, a short pause. In between, the unit will announce
“Warning Carbon Monoxide!”. In a Smoke incident, the horn will sound
in the repetitive manner -- three (3) beeps, a pause, three (3) beeps, a
pause. In between, the unit will announce “Fire! Fire!”.

The unit shall also indicate a low battery warning utilizing each of the

following methods: a brief alarm chirp, the voice announcement of “Low
Battery!” and the red LED will flash once per minute. The unit shall incor-
porate 2 LED’s. A green LED will flash when power is present. A red LED
will flash once every 30-40 seconds to indicate the alarm is operating
properly and will flash once per second when the unit is alarming and
will remain so until the air is cleared.

The unit shall at a minimum meet the requirements of UL 2034,

UL217, NFPA72, (chapter 11 2002 edition) The State of California Fire
Marshall, NFPA101 (One and two family dwellings) Federal Housing
Authority (FHA), Housing and Urban Development (HUD). It shall also
include a 5-year manufacturer’s limited warranty.

Technical Specifications

Unit Number:

900-0102

Model:

KN-COSM-B

Power Source:

3 AA Battery

Sensors:

Smoke: Ionization, CO: Fuel Cell

Audio Alarm:

85dB at 10ft

Temperature Range:

40˚F (4.4˚C) to 100˚F (37.8˚C)

Humidity Range:

5%-95% relative humidity

Size:

5.75” in diameter x 1.7” depth

Weight:

13oz

Interconnects:

No

Ordering Information

UPC: 7 84908 01020 9

Part

Dimensions

Case/

Layers/

Skid

Number

I 2 of 5

Pack Quantity

(w x d x h inches)

Weight

Skid

Skid

Weight

900-0102-02

107-84908-01020-6

PDQ (3 units)

8.0 x 11.25 x 6.25

2.5lbs

150

3

375lbs

900-0102-16

207-84908-01020-3

Cut Case (20 units)

16 x 12 x 21.8

18lbs

18

3

325lbs

900-0102-37

307-84908-01020-0

Power Tower (60 units)

20 x 24 x 41 (incl. pallet)

50lbs

3

3

150lbs

CUT CASE

POWER TOWER

PDQ

3

20

60

5.75"

1.7"