Maintenance and annual startup, Service technician, Owner maintenance – Lochinvar Knight XL 399 - 800 User Manual

Page 65: Maintenance

Advertising
background image

Installation & Operation Manual

65

Maintenance and annual startup

Table 12A Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

General:

• Address reported problems

• Inspect interior; clean and vacuum if

necessary;

• Clean condensate trap and fill with fresh

water

• Check for leaks (water, gas, flue,

condensate)

• Verify flue and air lines in good condition

and sealed tight

• Check system water pressure/system

piping/expansion tank

• Check control settings

• Check ignition and flame sense

electrodes (sand off any deposits; clean
and reposition)

• Check wiring and connections

• Perform start-up checkout and

performance verification per Section 10.

• Flame inspection (stable, uniform)

• Flame signal (at least 10 microamps at

high fire)

• Clean the heat exchanger if flue

temperature is more than 54°F (30°C)
above return water temperature.

If combustion or performance
indicate need:

• Clean heat exchanger

• Remove and clean burner using

compressed air only

• Clean the blower wheel

ANNUAL

ST

ART

-UP

Owner maintenance

(see the Knight XL User’s Information Manual for

instructions)

Daily

• Check boiler area

• Check pressure/temperature

gauge

Monthly

• Check vent piping

• Check air piping

• Check air and vent termination

screens

• Check relief valve

• Check condensate drain system

• Check automatic air vents

Periodically

• Test low water cutoff (if used)

• Reset button (low water cutoff)

Every

6 months

• Check boiler piping (gas and

water) for leaks

• Operate relief valve

End

of season

months

• Shut boiler down (unless boiler

used for domestic hot water)

12

Maintenance

Advertising