General, Venting – Lochinvar KNIGHT XL 801 User Manual

Page 18

Advertising
background image

18

3

General

venting

6. Priming

and

Cementing:

a.

Handle

fi ttings and pipes carefully to prevent

contamination

of

surfaces.

b. Apply a liberal even coat of primer to the fi tting

socket.

c. Apply a liberal even coat of primer to the pipe end to

approximately 1/2" beyond the socket depth.

d. Apply a second primer coat to the fi tting socket.

e. While primer is still wet, apply an even coat of

approved cement to the pipe equal to the depth of

the

fi tting socket.

f. While primer is still wet, apply an even coat of

approved cement to the fi tting socket.

g. Apply a second coat of cement to the pipe.

h. While the cement is still wet, insert the pipe into the

fi tting, if possible twist the pipe a 1/4 turn as you insert

it.

NOTE: If voids are present, suffi cient cement was

not applied and joint could be defective.

j.

Wipe excess cement from the joint removing ring or

beads as it will needlessly soften the pipe.

Table 3A Vent Pipe, and Fittings

PVC/CPVC air intake/vent connections

1. Combustion Air Intake Connector (FIG.’s 3-9 and 3-10) - Used to provide combustion air directly to the unit from

outdoors. A fi tting is provided on the unit for fi nal connection. Combustion air piping must be supported per guidelines

listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate.

2. Vent Connector (FIG.’s 3-9 and 3-10) - Used to provide a passageway for conveying combustion gases to the outside.
Transition

fi ttings are provided with the unit for fi nal connection. Vent piping must be supported per the National Building

Code, Section 305, Table 305.4 or as local codes dictate.

6” COUPLING

(FIELD SUPPLIED)

6” CPVC

STARTER

PIECE

(FACTORY SUPPLIED)

VENT

AIR

THE 6” STAINLESS STEEL ADAPTER SUPPLIED
WITH THE BOILER MUST BE USED FOR VENT
CONNECTION TO PVC/CPVC. THE 6” CPVC
STARTER PIECE MUST BE USED FOR PVC ONLY.

Figure 3-10 Near Boiler PVC/CPVC Venting - Models
701 - 801

VENT

AIR

4" CPVC PIPE SUPPLIED WITH
BOILER MUST BE USED FOR VENT CONNECTION

NOTE: CPVC VENT OR STAINLESS STEEL PIPE AND
VENT FITTINGS MUST BE USED IN CLOSET AND
ALCOVE INSTALLATIONS.

*

* 4” CPVC STREET ELBOW
MAY BE SUBSTITUTED

Figure 3-9 Near Boiler PVC/CPVC Venting - Models 400 - 601

*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking precaution to ensure
no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially designed adapters and sealing method,
see manufacturer’s instructions.

Installation & Operation Manual

All vent pipe materials and fi ttings must comply with the following:

Item

Material

Standards for installation in:

United States

Canada

Vent pipe and

fi ttings

PVC Plastic Pipe, Schedules 40, 80, & 120

ANSI/ASTM D1785

CPVC and PVC venting must be ULC-S636

Certifi ed. IPEX is an approved manufacturer

in Canada supplying vent material listed to

ULC-S636.

PVC Plastic Pipe Fittings, Schedule 40

ANSI/ASTM D2466

PVC Plastic Pipe Fittings, Schedule 80

ANSI/ASTM D2467

PVC - DWV Pipe and Fittings

ANSI/ASTM D2665

CPVC Plastic Pipe, Schedule 40 & 80

ANSI/ASTM F441

CPVC Plastic Pipe Fittings, Schedule 80

ANSI/ASTM F439

AL29-4C

UL1738

ULC-S636

NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE

Approved Stainless Steel Vent Manufacturers

Make

Model

ProTech Systems (Simpson Dura-Vent Co.)

FasNSeal Vent / FasNSeal Flex* Vent

Z-Flex (Nova Flex Group)

Z-Vent

Heat Fab (Selkirk Corporation)

Saf-T Vent