4 Chapter 4 - Specifications

4.1 General Specifications

• Manual and Automatic Transfers
• Sense and transfer time – less than 6 milliseconds
• Break-Before make switching
• Selectable preferred source
• Selectable auto/manual retransfer
• In-phase transfer window – adjustable from 5 ± 1°
• Convection cooling
• Hot swappable electronic static switching module
• Live mimic on Hot swappable unit for indicating load supply status & alarms
• Make before break manual bypass switch to transfer load from static switch to direct source 1 or source 2

4.2 Electrical Specifications


ELECTRICAL

CHARACTERISTICS

UNITS

DESCRIPTION

Nominal Input Voltage

Volts

110, 115 or 120 volts singe phase, 3W+G, 50 Hz. Solidly grounded

power sources

Nominal Output current

Amps

25

Frequency

Hz

50 / 60

Source unhealthy status

-

Guaranteed Transfer to alternate source within –15 % of Vnominal

Load Power factor range

-

0.5 to unity leading or lagging

Load Crest factor

-

upto 3.5

In-Phase transfer window

-

Adjustable from 5 ± 1º

Source voltage distortion

%

up to 10% THD

Overload capability

%

125% of continuous current for 2 hrs, 1000% for two cycles minimum.

Over current Protection

-

By semi conductor fuse

Short circuit withstand

capability

Amps

upto 20,000 symmetrical amps, protected by internal fusing.

Redundant Control Power

supplies

-

taken from available source 1 and source 2

Integral Maintenance Bypass

-

Make before break operation

Alarm contacts

-

Eight Isolated Normally Open alarm & static switch Status contacts.

Unsynchronised transfer

6 milllisec for synchronized transfer and 16 millisec for unsynchronized

transfer.