114195 – System Users Manual

12

Table 5.4 Program Functions

Parameter

Format

Factory Default

Date

MM/DD/YY (Month, Date, Year)

Current Date

Time

HH/MM (Hours, Minutes)

Eastern Stand Time

Monthly Test Date

DD (Date)

15

th

of the Month

Monthly Test Time

HH/MM (Hours, Minutes)

5:00

Yearly Test Date

MM (Month)

01

Yearly Test Time

HH/MM (Hours, Minutes)

8:00

Load Reduction

AAAA(Amps)

0.0A

Low VAC Alarm

VVVV(Volts)

1.0V

High VAC Alarm

VVVV(Volts)

999.9V

Ambient Temp Alarm DDD(Degrees Centigrade)

70°C

Near Low Battery

VVVV(Volts)

See Table 5.5



Near Low Battery Voltage is in VVVV (Volts). The last digit entered is after the decimal place.
I.E. (430 + ENTER) will register 43.0VDC. Please refer to table 5.5.


Load Reduction Fault is in AAAA (Amps). The last digit entered is after the decimal place.
I.E. (480 + ENTER) will register 48.0 Amps. If the output current under battery power is 10
percent below this number, the alarm will be set.


Low AC Voltage Alarm is in VVVV (Volts). The last digit entered is after the decimal place.
I.E. (1200 + ENTER) will register 120.0 Volts. If the Input AC Voltage goes below this number
the alarm will be set.


High AC Voltage Alarm is similar to Low AC Voltage Alarm.


Ambient Temperature Alarm is in DDD (Degrees Centigrade). I.E. (75 + ENTER) will register
75 deg. C. When the ambient temperature internal to the inverter enclosure goes above the
set point the alarm will be set.

Table 5.5 Near Low Battery Voltages

DC Voltage

Near Low Battery

48VDC 43VDC
72VDC 65VDC
96VDC 86VDC

120VDC 108VDC
144VDC 130VDC
180VDC 162VDC
240VDC 216VDC