Installation, Instructions, Warning – Lincoln Electric RANGER IM819-B User Manual

Page 12

Advertising
background image

A-5

INSTALLATION

RANGER 10,000

A-5

LOCATION / VENTILATION

The welder should be located to provide an unrestrict-
ed flow of clean, cool air to the cooling air inlets and to
avoid heated air coming out of the welder recirculating
back to the cooling air inlet. Also, locate the welder so
that engine exhaust fumes are properly vented to an
outside area.

STACKING

RANGER 10,000 machines cannot be stacked.

CONNECTION OF LINCOLN ELECTRIC
WIRE FEEDERS

Shut off welder before making any electrical
connections.
------------------------------------------------------------------------
WIRE FEED (CONSTANT VOLTAGE)
CONNECTION OF LN-15 ACROSS-THE-ARC WIRE
FEEDER
The LN-15 has an internal contactor and the electrode
is not energized until the gun trigger is closed. When
the gun trigger is closed the wire will begin to feed and
the welding process is started.

a. Shut the welder off.
b. Connect the electrode cable from the LN-15 to

the“ELECTRODE” terminal of the welder. Connect
the work cable to the “TO WORK” terminal of the
welder.

c. Set the Polarity switch to the desired polarity, either

DC (-) or DC (+).

d. Attach the single lead from the front of the LN-15

to work using the spring clip at the end of the lead.
This is a control lead to supply current to the wire
feeder motor; it does not carry welding current.

e. Set the “RANGE” switch to the “WIRE FEED-CV”

position

f. Place the Engine switch in the “High Idle” position.
g. Adjust the wire feed speed at the LN-15 and adjust

the welding voltage with the output “CONTROL” at
the welder. Output “CONTROL” must be set above 3.

Note: LN-15 Control Cable model will not work with

the RANGER 10,000.

CONNECTION OF THE LN-25 TO THE

RANGER

10,000

a.

Shut the welder off.

b.

Connect the electrode cable from the LN-25 to
the“ELECTRODE” terminal of the welder.
Connect the work cable to the “TO WORK” termi-
nal of the welder.

c.

Position the welder “Polarity” switch to the desired
polarity, either DC (-) or DC (+).

RANGER 10,000

Constant Current

225 Amps AC @ 25 Volts
210 Amps DC @ 25 Volts

Constant Voltage

200 Amps DC @ 20 Volts

d.

Position the “RANGE” switch to the “WIRE FEED”
position.

e.

Attach the single lead from the LN-25 control box
to the work using the spring clip on the end of the
lead - it carries no welding current.

f.

Place the engine switch in the “AUTO” position.

g.

Adjust wire feed speed at the LN-25 and adjust
the welding voltage with the output “CONTROL”
at the welder.

NOTE: The welding electrode is energized at all
times, unless an LN-25 with built-in contactor is used.
If the output “CONTROL” is set below “3”, the LN-25
contactor may not pull in.

CONNECTION OF K930-2 TIG MODULE TO THE
RANGER 10,000.

The TIG Module is an accessory that provides high
frequency and shielding gas control for AC and DC
GTAW (TIG) welding. See IM528 supplied with the
TIG Module for installation instructions.

Note: The TIG Module does not require the use of a
high frequency bypass capacitor. However, if the
RANGER 10,000 is used with any other high frequen-
cy equipment, the bypass capacitor must be installed,
order kit T12246.

INSTRUCTIONS

ADDITIONAL SAFETY PRECAUTIONS

Always operate the welder with the roof and case
sides in place as this provides maximum protection
from moving parts and assures proper cooling air flow.

Read and understand all Safety Precautions before
operating this machine. Always follow these and any
other safety procedures included in this manual and in
the Engine Owner’s Manual.

WELDER OPERATION

WELDER OUTPUT
• Maximum Open Circuit Voltage at 3700 RPM is

80 Volts RMS.

• Duty Cycle is the percentage of time the load is

being applied in a 10 minute period. For example, a
60% duty cycle represents 6 minutes of load and 4
minutes of no load in a 10 minute period. Duty Cycle
for the RANGER 10,000 is 100%.

WARNING

Advertising