Building Safety. Building Security.

Description

The Fire Brigade Interface FWI016 allows for the con-

nection of two independent transmitting devices for di-

rect interconnection to a designated alarm respondent

(e.g., the fi re brigade) as well as the connection of a

country specifi c fi re brigade control unit to Fire Detec-

tion Control Panels Series BC016.

A dry contact and a line-monitored output are available

for the connection of the transmitting devices.

The parameters of the eight inputs and seven outputs

can also be freely set and thus are available for general

control tasks.

• Relay output with dry changeover

contact

• Line-monitored output with selectable

surveillance current

• 8 inputs and 7 outputs for control

tasks

• Connection of country-specifi c fi re

brigade control units

Specifi cations

Current consumption at 24V

typ. 4mA

Contact rating of relay contact

60V/1A/30W

Contact life

approx. 300,000 switching cycles (at 24VDC/1A)

Ambient temperature

-5°C to +50°C

Dimensions L × W × H

130 Ч 65 Ч 15 (mm)

Weight

70g

Part No.

210111

Order name

Fire Brigade Interface FWI016-1