LST Vds MEA244-1 User Manual

LST Hardware

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

MEA244-1_DBL_LST_EN_0823.PDF • PAGE 1

A

Building Safety. Building Security.

Description

• ADM loop technology with

System Sensor/200 protocol

• 4 independent line-monitored inputs
• 4 independent outputs with patented

monitoring of line resistance and

load resistance

• Optimized for use in extinguishing

systems

• Supply supervised for undervoltage

The Multi Module MEA244-1 has been designed espe-

cially for use in extinguishing systems. It has 4 indepen-

dent inputs for connection of contact detectors, and 4

independent, powerful outputs for actuation of external

control devices.

The inputs are monitored to detect wire breakages and

short circuits of the connection leads. On the outputs

the internal resistances of the control devices and the

line resistances are monitored separately. An automatic

calibration procedure, which gets started by pressing

a key during commissioning, determines the reference

values of both resistances. The patented method of

multiple monitoring makes the reliable detection of line

or load faults as well as contact corrosion possible.

The multi module is used as loop element with inte-

grated dual-isolator, in an ADM loop with System Sen-

sor/200 protocol. The module occupies 8 consecutive

addresses on the ADM loop. During commissioning, the

base address, which is assigned to input 1, gets ente-

red using a key, all further addresses are automatically

assigned by the module.

The MEA244-1 and the connected control devices are

supplied through an external 24V power supply. The

supply voltage gets supervised for undervoltages. If the

voltage drops below the threshold of the undervoltage

detection, then this event is automatically signalled to

the control panel, via the loop, as fault of all four out-

puts. Each input and each output has a status LED.

The multi module is available in two versions:

• The MEA244-1/TR has been designed for mounting

on a DIN rail,

• the MEA244-1/E can be mounted in a control panel

using the supplied mounting spacers.