PRE-OPERATION SERVICE

READ the engine operating and maintenance instruc-
tions supplied with this machine.
------------------------------------------------------------------------

OIL

This unit is supplied from the factory with the engine
crankcase filled with a high quality SAE 10W/30 oil.
This oil should be acceptable for most typical ambient
temperatures. Consult the engine operation manual
for specific engine manufacturerʼs recommendations.
Upon receipt of the welder, check the engine dipstick
to be sure the oil is at the “full” mark. DO NOT overfill.

FUEL

Fill the fuel tank with the grade of fuel recommended
in the Engine Operatorʼs manual. Make sure the valve
on the water separator is in the open position.

COOLING SYSTEM

The radiator has been filled at the factory with a 50-50
mixture of ethylene glycol antifreeze and water.
Check the radiator level and add a 50-50 solution as
needed (see engine manual or antifreeze container for
alternate antifreeze recommendations).

CAUTION

A-4

INSTALLATION

CLASSIC® 300D KUBOTA

A-4

TRAILER (See Optional Features)

If the user adapts a non-Lincoln trailer, the user must
assume responsibility that the method of attachment
and usage does not result in a safety hazard nor dam-
age the welding equipment. Some of the factors to be
considered are as follows:
1. Design capacity of trailer vs. weight of Lincoln

equipment and likely additional attachments.

2. Proper support of, and attachment to, the base of

the welding equipment so there will be no undue
stress to the framework.

3. Proper placement of the equipment on the trailer to

ensure stability side to side and front to back when
being moved and when standing by itself while
being operated or serviced.

4. Typical conditions of use, i.e., travel speed, rough-

ness of surface on which the trailer will be operat-
ed; environmental conditions, likely maintenance.

5. Conformance with federal, state and local laws. (1)

(1) Consult your federal, state and local laws regarding specific

requirements for use on public highways.

POLARITY CONTROL AND CABLE SIZES

With the engine off, route the electrode and work
cables through the strain relief bracket on the base
and connect to the studs located below the fuel tank
mounting rail. (See size recommendations below.)
For positive polarity, connect the electrode cable to
the terminal marked “+”. For Negative polarity, con-
nect the electrode cable to the “-” stud. These con-
nections should be checked periodically and tightened
if necessary.

When welding at a considerable distance from the
welder, be sure you use ample sized welding cables.

RECOMMENDED COPPER CABLE SIZES

Cables Sizes for Combined Length
of Electrode Plus Work Cable

Amps

Duty Cycle Up to 200ft.(61m) 200 to 250ft.

(61 to 76m)

250

100%

1

1/0

300

60%

1/0

2/0

VEHICLE MOUNTING

Improperly mounted concentrated loads may
cause unstable vehicle handling and tires or other
components to fail.

• Only transport this Equipment on serviceable

vehicles which are rated and designed for such
loads.

• Distribute, balance and secure loads so vehicle

is stable under conditions of use.

• Do not exceed maximum rated loads for compo-

nents such as suspension, axles and tires.

• Mount equipment base to metal bed or frame of

vehicle.

• Follow vehicle manufactureʼs instructions.

------------------------------------------------------------------------

WARNING

• Stop engine while fueling.
• Do not smoke when fueling.
• Keep sparks and flame away

from tank.

• Do not leave unattended while

fueling.

• Wipe up spilled fuel and allow

fumes to clear before starting
engine.

• Do not overfill tank, fuel expan-

sion may cause overflow.

DIESEL FUEL ONLY-Low sulphur fuel or ultra low
sulphur fuel in U.S.A. and Canada.
------------------------------------------------------------------------

WARNING

DIESEL FUEL

can