Liebert IntelliSlot OC-485 User Manual

Liebert intellislot, Oc-485 card, Quick start guide i

Advertising
background image

Liebert IntelliSlot

®

OC-485 Card

Quick Start Guide

I

NSTALL

• Locate the Intellislot option bay for your Liebert equipment. You might

need to remove a plastic cover.

• Insert the Liebert IntelliSlot OC-485 Card into the Intellislot bay.
• Secure the card with the supplied screws.
• Connect RS-485 cable.
IGM: The card ships with IGM service enabled. (No configuration is

required for IGM communications.)
Modbus: To assign a server ID address, use the Service Terminal to con-

figure the card. Proceed to Steps 2 & 3.

C

ONNECT

THE

C

ABLE

• Locate the blue serial configuration cable (null modem) that shipped

with the card.

• Connect the configuration cable to the DB-9 port on the card and to a

COM port on your PC.

C

ONFIGURE

THE

C

ARD

• Use terminal emulation soft-

ware, such as HyperTerminal™,

to open a direct connection to

the card.

• Press ENTER for the Main

Menu, above right.

• Select option 1 and press Enter

to access the communications

settings, shown at right.

• Enter 1 and press enter to

enable the Modbus application.

• At the next screen, enter 3 to

access the screen to set the

server ID for the Liebert

IntelliSlot OC-485 Card (the ID

default is 1, but may be any

number up to 255). In the

example at right, the server ID

is “2.”

• Press Esc to return to the main

Menu.

• Enter X and press Enter to exit

HyperTerminal, save your

changes and reboot the card.

Baud Rate:

9600

Data Bits:

8

Parity:

None

Stop Bits:

1

Flow Control:

None

NOTE

When installing the card in a Liebert NX

, configure the

communication port of the Liebert NX to 2400 baud. Refer to the

Liebert NX user manual for instructions.