Lightolier Emergency Lighting E6 Series User Manual

E6 series, Commercial emergency lighting

Advertising
background image

E6 Series

Commercial Emergency Lighting

Page 1 of 2

Job Information

Type:

Job Name:

Cat. No.:

Notes:

Features

Illumination: Illumination

is provided by two fully-

adjustable polycarbonate lamp

heads. Each lamp head utilizes

a high-performance parabolic

reflector in conjunction with a

6 VDC, 5.4 W T-5 wedge base

tungsten lamp. High-impact

acrylic refractors minimize

glare and maximize optic

control.

Housing: Constructed of

impact resistant , UL 94 V-0,

5 VA thermoplastic, completely

self-contained. White housing

is standard, with an optional

black housing available.

Operating Temperature

Range: Damp Location

68°F (20°C) to 104°F (40°C)

Diagnostic Electronics

(standard): 120/277 VAC

dual voltage input with surge-

protected, solid-state charging

circuitry provides for a reliable

charging system. Charging

system is complete with

low voltage disconnect, AC

lockout, brownout protection,

AC indicator lamp and test

switch.

Self-Testing Diagnostics

(optional): Continuously

monitors the critical functions

of the equipment, including:

battery disconnect, battery

failure, charger failure,

transformer failure and lamp

failure. Self-Testing routine

performs a one-minute test

every 30 days, a 30-minute

test on the 6th month and a

90-minute test annually.

Electrical Specifications:

0.045 A (120 VAC)

0.020 A (277 VAC)

Code Compliance

UL 924 and UL damp location

listed. NFPA 101, NEC, BOCA,

OSHA and IBC illumination

standards.

Warranty

Three year full electronics

warranty. One year full plus

four year prorated battery

warranty.

E611

16.0"

(40.6 cm)

5.0"

(12.7 cm)

11.87"

(30.15 cm)

Advertising