System Input/Output Ratings

Warranty

Standard Warranty
Lightolier will provide parts and on-site labor for the first 90 days following
shipment of product, and parts only for an additional 270 days.

Extended Warranty
(Available with purchase of Factory Start-Up Service) Lightolier will provide
parts and on-site labor for the first 12 months following start-up of the
product, and parts only for an additional 12 months.

System One-Line Diagram

Pin

Description

Function

8

Normal

System Functioning Normally

6

Load On Reserve

Double Conversion Inverter Not Operating

9

Power Failure

Load Supplied by Battery

7

End of Discharge Period

Unit Will Soon Stop Operating

5

Common

Common Connection to Above 4 Signals

Computer Interface Pin Configuration

(AS/400™)

Listed to

UL 924

SYSTEM

INPUT

INPUT

AVAILABLE OUTPUT VOLTAGES/

OCB POLE SPACES

RATING

VOLTAGE

AMPS

1

MAX. LOAD AMPS

2

AVAILABLE

120 V

208 V

240 V

277 V

12,000 VA

277

54.5

100.0

43.3

12

208/240

69.7/60.4

100.0

57.7

50.0

12

NOTES:
1) Continuous Duty
2) Total Load Not to Exceed System Rating

Lightolier

a Genlyte Thomas Company

www.lightolier.com

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504

Job Information

Type:

Electrical (continued from page 1)

• Automatic, battery protecting low voltage disconnect (LVD)
• Advanced battery diagnostics and management system
• Temperature compensated battery charger
• 24 hour recharge time
• High frequency, very low ripple current charger
• Input and output disconnect switch
• Battery disconnect switch

Battery

Maintenance free, sealed lead calcium battery has an estimated service life of
10 years, and an operating temperature range of 65°F (19°C) to 85°F (30°C).

Options