Building Safety. Building Security.

• Addressable conventional technology
• Combination of optical and thermal

characteristics of fi re

• Individual detector addressing by

means of optional address module

• Optional connection of remote

indicator

• Sealed electronics

Description

The Optical-Thermal Detector OH-13001 uses both the

scattered light principle as well as a separate thermal

detection unit. It was developed to detect the characte-

ristics of fi re in a wide range of applications, and to avo-

id deceptive alarms. The modern design of both measu-

rement systems and the analysis of the parameters by

means of a special algorithm allow to reliably evaluate

the characteristics of fi re. This makes it an all-rounder

that is used in virtually all fi elds of fi re detection.

Intelligent evaluation algorithms compensate for the

contamination of the optical measurement system,

thus keeping the response sensitivity of the detector

constant for a long time. In this way, false alarms can

be avoided to a great extent. If the contamination can

not be compensated any further, or if a fault occurs in

the measurement system, this is indicated by a yellow

fl ashing of the multicoloured status LED.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. By

means of the optional Address Module NG60-1, each

detector can be addressed individually, thus allowing to

display the detector address, as well as an assigned

element text, on a suitable fi re detection control panel.

The detector can be attached to various bases and it

can be protected against theft.

Specifi cations

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 65µA (quiescent)

Ambient temperature

- 40°C to +70°C (no condensation or icing)

Relative humidity

0 – 98% (no condensation)

Dimensions ш Ч H

100 × 42 (mm)

Colour

white

Weight

80g

Approval

VdS G204040

Order number

241061

Order name

Optical-Thermal Detector/Conv./ORBIS/Apo OH-13001