LST MCP5A Series User Manual

Specifi cations description

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

MCP5A_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Specifi cations

Description

The Manual Call Points Series MCP5A are certifi ed to

the standard EN 54-11/A and are designed for use in

ADM loops with System Sensor/200 protocol.

Two mechanical versions of the detector are available:

• With pane of glass: The detector is activated by

pressing in the pane of glass, which breaks into

two pieces at a predetermined breaking point. By

means of a special key, the detector case can be

opened and the pane of glass can be replaced.

• With pane of plastic: The detector is activated by

pressing in the pane of plastic without breaking it.

By means of a special key, the pane can be put

back to the idle position, thereby resetting the de-

tector.

Each of these two mechanical versions is available with

or without dual-isolator. The integrated dual-isolator dis-

connects the adjacent loop elements fast and safely in

case of a short circuit.

The activated condition of the manual call point is opti-

cally indicated by an LED. The detector address is se-

lected with two decadic rotary switches.

The detector is fi tted into a plastic case and can be

mounted on a 60mm fl ush-mount installation box. An

optional case for surface mounting on a wall can be

supplied.

• ADM loop technology with

System Sensor/200 protocol

• Available with pane of glass or plastic
• LED indicates activation
• Versions with or without dual-isolator
• Operating instructions by means of

standardised symbols

Operating voltage

Supply through loop voltage

Ambient temperature

-10°C to +55°C (no condensation or icing)

Relative humidity

max. 95% (no condensation)

Protection class

IP24

Dimensions W × H × D

89 Ч 93 Ч 28 (mm)

Colour

fl ame red, RAL 3000

Weight

110g

Approval

LPCB 166b/45, 166b/46

Manual call point with pane of glass, without isolator MCP5A-RP07FG

Current consumption

260µA (quiescent)

Order number

245040

Order name

Manual Call Point/Red/200/Glass MCP5A-RP07FG