LST ES58-2 User Manual

Description specifi cations

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

ES58-2_DBL_LST_EN_0805.PDF • PAGE 1

A

Building Safety. Building Security.

Description

Specifi cations

The Safety Barrier ES58-2 for the galvanic isolation of

the detectors in the hazardous area serves for the de-

sign of an intrinsically safe electric circuit. The plastic

surface-mount housing allows to mount the safety bar-

rier near the hazardous area.

The built-in zener barrier limits the current and the vol-

tage of the detector line, as well as the electric energy

stored in the intrinsically safe circuit. The maximum

number of detectors depends on the country-specifi c

regulations and can be found in the Connection of De-

tectors.

Due to the galvanic isolation, the earth leakage moni-

toring can remain activated in the fi re detection control

panel. Thus, the installation can also be monitored in

the hazardous area.

• Allows to create intrinsically safe

circuits

• Galvanic isolation of the detector line

voltage

• Connection of intrinsically safe

detectors

• Industrial plastic surface-mount case
• ATEX certifi ed

Ignition protection

intrinsically safe

Ex classifi cation

EEx ia llC

Operating voltage

Supply through the detector line voltage

Quiescent current

approx. 5mA

Ambient temperature

-20°C to +60°C

Dimensions W × H × D

120 Ч 160 Ч 90 (mm)

Colour

light grey, similar to RAL 7035

Weight

650g

Approval

BASEEFA98ATEX7343

Order number

228003

Order name

Safety Barrier/Conv. ES58-2

Advertising