Checklist for Liebert XDP Startup

19

3.1.1 Calculating Refrigerant Charge—Example

Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert

XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant

required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF,

Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20

Liebert XDV8 cooling modules.
Table 10

Calculating refrigerant charge—example

Components

Number of Units

or Piping Length,

feet

Pounds Per

Component

Total, lb.

Liebert XDP

1

157

157

Liebert XDV8 Cooling Modules

20

2.32

46.4

Supply Main, 1-1/8"

100

0.45

45

Return Main, 2-1/8"

100

0.28

28

Liebert XDV 1/2" supply Liebert XD Flex Pipes

20

0.8

16

Liebert XDV 5/8" return Liebert XD Flex Pipes

20

0.03

0.6

Total

293

Table 11

Worksheet to calculate refrigerant charge

Components

Number of Units

or Piping Length

Pounds Per

Component

Total

Total