Unit operation – Lochinvar 1.5 User Manual

Page 15

Advertising
background image

15

5

Unit Operation

(continued)

Demand Confi guration: ENABLE = INACTIVE; BMS = ACTIVE

In this confi guration the unit is controlled by setting the modulation setpoint from 0 - 100%, or the setpoint. The setpoint
command will be determined by the parameters in the control.

Rate command will be 0 - 100% of the modulation range.

All sensors and limiting devices should be hardwired to the terminal strip on the back of the unit excluding the 0 - 10Vdc signal.
This signal will be sent to the unit via ModBus.

The holding registers will need to be set as follows:

Holding Registers

Defi nition

Bit Value (HEX)

Action

40001

Confi guration

00 04

Set Confi guration to read 40003

40003

Rate Command

00 00

Sets Modulation % or Setpoint

For proper hexadecimal conversion of rate percentage, please refer to the Rate and Temperature Conversion section on page 17
of this manual.

NOTE: To ensure proper operation re-send the confi guration bits to holding register 40001 prior to issuing a command.

Hot Water Generation

Hot water generation can be accomplished with one of two methods when a Crest boiler is connected to a BAS system, DHW
with direct control, and DHW with remote control.

DHW with direct control:

This is the typical installation with a hot water generator in close proximity to the boiler with the tank thermostat, or tank
temperature sensor, wired to the terminal strip of the unit.

Demand Confi guration: ENABLE = ACTIVE; BMS = ACTIVE

In this confi guration the unit is controlled by providing an enable signal. The setpoint command will be determined by the
parameters in the control and a rate command through ModBus communications.

The rate command will be 0 - 100% of modulation.

All sensors and limiting devices should be hardwired to the terminal strip on the back of the unit excluding the enable and 0-10V
BMS signal. These signals will be sent to the unit via ModBus.

The holding registers will need to be set as follows:

Holding Registers

Defi nition

Bit Value (HEX)

Action

40001

Confi guration

00 05

Set Confi guration to read 40002 & 3

40002

Coils 00

01

Enables

unit

(00 00 disables unit)

40003

Rate Command

00 ##

Sets Modulation % or Setpoint

NOTE: To ensure proper operation re-send the confi guration bits to holding register 40001 prior to issuing a command.

For proper hexadecimal conversion of rate percentage, please refer to the Rate and Temperature Conversion section on page 17
of this manual.

ModBus Instructions