Magnetom Harmony/Symphony Specifications

Fluid Specified

Water/Glycol

Max Heat Dissipation—BTUH (kW)

102,390

Fluid Temperature Range—°F (°C)

43-54 (6-12)

Fluid Flow Rate—GPM (l/m)

13 (50)

Fluid Pressure Drop—PSI (kPa)

21.8 (150)

Process Fluid Chiller Specifications

Model Number

CS135A

Fluid Circulated

Water

Net Cooling Capacity—BTUH (kW)

116,000 (34)

Leaving Fluid Temperature—°F (°C)

45 (7.2)

Fluid Flow Rate—GPM (l/m)

24 (91)

Harmony/ Symphony Pressure Drop—PSI (kPa)

21.8 (150)

Chiller Pressure Drop—PSI (kPa)

11.7 (81)

Pump Total Head—PSI (kPa)

56.3 (388)

Pump HP (kW)

3 (2.2)