LST M500RFE-AS User Manual

LST Safety

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

M500RFE-AS_DBL_LST_EN_0906.PDF • PAGE 1

A

Building Safety. Building Security.

• ADM loop technology with

System Sensor/200 protocol

• Up to 99 automatic detectors and 98

manual call points can be controlled

• Multi-language operating menu
• High range of radio transmission
• Two frequency bands (868/434MHz)

with automatic change-over

• Channel checked for availability

Description

Specifi cations

Operating voltage

10 – 30VDC

Current consumption external supply (at 24V)

max. 80mA

Current consumption from loop

325µA (quiescent)

Range of radio transmission (free air)

300m

Frequency band

868MHz or 434MHz

Ambient temperature

-10°C to +55°C

Dimensions W × H × D

210 Ч 270 Ч 70 (mm)

Colour

white/black

Weight

930g

Approval

VdS G208132

Order number

249202

Order name

RF Interface/Anal./SS M500RFE-AS

The RF Interface M500RFE-AS serves as a gateway

between radio detectors and a Fire Detection Control

Panel Series BC216. The communication with the con-

trol panel is established via the ADM loop with System

Sensor/200 protocol.

The RF interface can communicate with up to 99 auto-

matic radio detectors and up to 98 manual radio call

points. For each automatic radio detector one detector

is parameterised in the fi re detection control panel, and

for each manual radio call point one module is para-

meterised. The gateway itself occupies one module

address on the loop.

The detectors are confi gured at the RF interface by

means of the automatic learning process. A manual pa-

rameterisation is also possible.

The RF interface is operated and confi gured using

the built-in key pad and the alphanumeric display. The

multi-language operating menu serves for the parame-

terisation as well as for displaying the signal strength

of any individual detector. A 6-digit authorisation code

provides protection against unauthorised access. Three

LEDs indicate the interface conditions operation, alarm

and fault.

The RF interface is designed for indoor surface moun-

ting and is equipped with a dual-isolator, which discon-

nects the loop in case of a short circuit.

Advertising