After the confirmation of the above conditions, prepare the wiring as follows:

1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring,

be guided by the circuit diagram pasted on the inside of control box cover.

2) Provide a circuit breaker switch between power source and the unit.

3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from

vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the
wires.)

4) Specification of power source

5) Confirm that electrical capacity is sufficient.

6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked

on the name plate.

7) Confirm that the cable thickness is as specified in the power sources specification.

(Particularly note the relation between cable length and thickness.)

8) Never fail to equip a leakage breaker where it is wet or moist.

9) The following troubles would be caused by voltage drop-down.

• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the

normal function of a overload protection device.

• Proper starting power is not given to the compressor.

Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning,
temperature control, etc.).

If Error Code happens in the display of indoor.

HAND OVER

Error Code

Error Contents

Checking Point

Indoor Air Sensor Open or Short

Indoor Pipe Sensor Open or Short

Outdoor Air Sensor Open or Short

Outdoor Pipe Sensor Open or Short

Communication failure between
Indoor and outdoor unit.

C0

C1

C3

C4

C5

1.Check Sensor Connection to PCB whether it's

connected well or not.

2.Replace it with new Sensor.

1.Check connecting cable wiring order between

Indoor and outdoor diagram.

2.Check all wire connector whether it is connected

or not.

3.Indoor AC PCB defects.(short inside).
4.Outdoor PCB defects.(short inside)

Advertising