Features

1. Upper Reflector: Clear anodized aluminum, 0.040" (16-ga.). Provides

wide beam distribution; can be removed for accessibility, inspection and
maintenance of ballast/junction box assembly.

2. Aperture Cone: Provides 55° visual cut-off to lamp and lamp image;

self-flange in painted white or aperture-matching polished flange. Consult
factory for other finishes.

3. Socket Cup: Galvanized steel, pre-wired with medium base pulse rated

socket. Snaps onto upper reflector for secure attachment without tools;
unitized construction assures proper lamp alignment to optics for consistent
performance.

4. Mounting Frame: 0.048" (18-ga.) galvanized steel includes pre-installed

mounting bars.

5. Mounting Ring: 0.048" (18-ga.) galvanized steel. Designed for vertical

adjustment from above or below for ceilings from 0" to 2" thick. Center-line
notches allow consistent alignment of multiple fixtures

6. Aperture Cone Retention Springs: Rust resistant springs secure cone in

place for quick, tool-less installation.

7. Frame Vertical Adjustment Mechanism: Vertical adjustment mechanism

accommodates mounting to virtually any ceiling system using pre-installed
mounting bars, or 1/2" EMT tubing (by others). Single locking feature secures
all adjustments. Alignment holes and markings allow fixture to be pre-set
prior to installation.

8. Mounting Bars: 0.048" (18-ga.) Pre-installed, telescoping bars extend to 30"

long and lock securely into position. Built-in locking tabs provide positive
attachment to common T-bar systems. Self-centering feature simplifies
installation in 24" O.C. grid systems. Attaches to steel or wood joists without
accessories.

9. Ballast: Electronic 120V or 277V. Magnetic dual voltage (120V & 277V).

Accessible from below for inspection and/or replacement without tools.

10.Junction Box: 0.048" (18-ga.) galvanized steel. UL listed for 8 No. 12 AWG,

90°C through branch circuit conductors; allows inspection from below.

11.Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do not

install insulation above nor within 3" (76mm) of any part of the luminaire.

Electrical

Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high-power factor,
T.H.D. <15%, thermally and transient protected, RMI / RFI complies with FCC
Part 18 non-consumer equipment, shut-down circuit at end of lamp life, sound
rating "A", -5°F minimum starting temperature, Type 1 outdoor rating.

Ceiling Cutout: 6 9/16” (167 mm) Dia.

Reflector Trim

Frame-In Kit

Lamp (Coated Ceramic, MH)

C6E17OHW CLW

Specular Clear, White Painted Flange.

CLP

Specular Clear, Matching Flange.

CCDW

Comfort Clear Diffuse, White Painted Flange.

CCDP

Comfort Clear Diffuse, Matching Flange.

CCZW

Champagne Bronze, White Painted Flange.

CCZP

Champagne Bronze, Matching Flange.

C670MHOE1

Electronic, 120V

70W E17, ED17, BD17 (Open Rated)

C670MHOE2

Electronic, 277V

70W E17, ED17, BD17 (Open Rated)

C610MHOE1

Electronic, 120V

100W E17, ED17, BD17 (Open Rated)

C610MHOE2

Electronic, 277V

100W E17, ED17, BD17 (Open Rated)

C670MHOU

Magnetic, 120V/277V 70W E17, ED17, BD17 (Open Rated)

C610MHOU

Magnetic, 120V/277V 100W E17, ED17, BD17 (Open Rated)

Electrical (cont.)

Ballast

ANSI Code

Voltage

Max. Amps

Input Watts

70W MH

M98/M139

120/277

0.67/0.29

78

100W MH M90/M140

120/277

0.90/0.43

110

Magnetic Ballast: 120/277V dual voltage, 60 Hz., encased and potted,
HX-HPF circuit type, high power factor, sound rating “B”, -20°F minimum
starting temperature, Type 1 Outdoor rating.

Ballast

ANSI Code

Voltage

Max. Amps

Input Watts

70W MH

M98/M143

120/277

1.90/0.80

94

100W MH M90/M140

120/277

2.40/1.10

125

Options and Accessories

Auxiliary: Add suffix A to Frame-In Kit and Reflector Trim. See Spec.Sheet “A/E”
Emergency Lamp: Add suffix E to FIK and Reflector Trim. See Spec.Sheet “A/E”
Slope Ceiling Adapters: See Specification Sheet SCA.
Fuse (magnetic ballast): Add suffix F1 or F2 to Frame-In Kit (F1=120V F2=277V)
Chicago Plenum: Consult Factory.

Labels

UL (Suitable for Damp Locations), CSA, I.B.E.W.
For 100W Electronic, install fixtures with minimum spacing: 2 feet from center-to-
center of adjacent luminaries; 1/2 inch from top of luminaire to overhead building
member; 1 foot from luminaire center to side building member.