Description

Specifi cations

The fi re detection control panels Series BC216 and

BC016, respectively, provide 16 freely programmable

open-collector control outputs. Eight of these outputs

are connected to a fl at cable connector. The Relay Mo-

dules RL58-1 and RL58-2 allow for the easy conversion

of these control outputs to dry changeover contacts.

The componentry is connected to the fi re detection con-

trol panel via a fl at cable.

The RL58-1 provides eight relay outputs with a maxi-

mum contact rating of 30W. The current is limited to 1A

and the voltage is limited to 60VDC. The RL58-2 offers

four relay outputs with a maximum of 5A/230VAC. The

terminal of the RL58-2 are designed for mains voltage.

Two relay modules RL58-2 are each cascadable via pin

connectors. The relay module is delivered with fl at ca-

ble and mounting accessories for easy installation.

• 8 or 4 relay outputs, respectively,

with one dry changeover contact

each

• Actuation display by LED for each

output

• Switch contacts on terminals
• Easy mounting on componentry

carrier

• Connection with control panel via fl at

cable

Operating voltage

20 – 31VDC

Current consumption at 24V

typ. 22mA per activated circuit

Control current

typ. 1.2mA per input

Ambient temperature

-5°C to +50°C

RL58-1

Switching power per contact

1A/60V/30W

Contact life

approx. 5 mill. switching cycles (unloaded)

approx. 300,000 switching cycles (at 24VDC/1A)

Dimensions L × W × H

85 Ч 65 Ч 37 (mm)

Weight

330g

Part No.

222004

Order name

Relay Module 8-Fold/60VDC RL58-1

Advertising