Table 6 battery run times, Table 6, Battery run times – Liebert GXT2-6000RT230 User Manual

Page 34

Advertising
background image

Troubleshooting

30

Using the configuration program, the user may specify the number of GXT2-240VBATT external bat-

tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 6 above shows the estimated run times at different loads.

Table 6

Battery run times

Load%

4500VA

6000VA

Internal Battery

(minutes)

10%

125

94

20%

66

46

30%

41

29

40%

30

21

50%

24

17

60%

19

13

70%

16

11

80%

14

9

90%

12

8

100%

10

7

Internal Battery

+ 1 External Battery

Cabinet (minutes)

10%

296

222

20%

166

124

30%

114

81

40%

86

60

50%

70

49

60%

56

39

70%

48

33

80%

41

28

90%

35

24

100%

31

21

Internal Battery

+ 2 External Battery

Cabinets (minutes)

10%

467

350

20%

262

197

30%

180

135

40%

142

105

50%

120

85

60%

98

70

70%

83

58

80%

72

50

90%

62

43

100%

54

38

Internal Battery

+ 3 External Battery

Cabinets (minutes)

10%

638

478

20%

358

269

30%

247

185

40%

193

145

50%

164

123

60%

138

101

70%

120

85

80%

104

73

90%

90

63

100%

80

55

Internal Battery

+ 4 External Battery

Cabinets (minutes)

10%

809

606

20%

454

341

30%

313

235

40%

245

184

50%

208

156

60%

175

131

70%

153

113

80%

135

97

90%

120

85

100%

106

75