Section 3: HARDWARE CONFIGURATION

DIP Switch Settings

The following user selectable operations are set by DIP SW1 on
the display panel circuit board: Refer to Table 2 and Figure 3.

Position

OFF

ON

1 Audible

beeper

enabled

Audible beeper
disabled

2 Remote

on/off

disabled. On/off
button affects MR1
operation only

Remote on/off of
Env. unit enabled.
Env. unit must have
remote on/off
capability, or MR1
will not be able to
perform this function

3

Optional alarm inputs
disabled

4 optional alarm
inputs enabled

4 Common

alarm

follows alarm
condition

Common alarm
de-energized when
alarm is silenced

Table 2: DIP Switch Settings

Note that factory default is OFF for all four positions.