Lennox Hearth ADAGIO-EN User Manual

Page 18

Advertising
background image

18

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Remember to maintain 1" (25 mm) clearance

to combustibles, framing members, and attic

or ceiling insulation when running vertical

chimney sections.

G. Support the vertical run sections -

See Section E on Page 15.

H. Change vent direction - At transition from or

to a horizontal/inclined run, install the SV4.5E45

and SV4.5E90 elbows in the same manner as

the straight vent sections. The elbows feature a

twist section to allow them to be routed about the

center axis of their initial collar section to align

with the required direction of the next vent run

element. Twist elbow sections in a clockwise

direction only so as to avoid the possibility of

unlocking any of the previously connected vent

sections (see Figure 18 on Page 15).

I. Continue installation of horizontal/inclined

sections - Continue with the installation of the

straight vent sections in horizontal/inclined run

as described in Step E. Install support straps

every 5 ft. (1.52 m) along horizontal/inclined

vent runs using conventional plumber’s tape.

See Figure 27, it is very important that the

horizontal/inclined run be maintained in a

straight (no dips) and recommended to be in

a slightly elevated plane, in a direction away

from the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal, though rise per foot

run ratios that are smaller are acceptable all the

way down to at or near level.

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides

for all vertical runs; and 3" (76 mm) at the top,

1" (25 mm) at sides, and 1" (25 mm) at the

bottom for all horizontal/inclined runs.

Use a carpenter’s level to measure from a

constant surface and adjust the support straps

as necessary.

HORIZONTAL (OUTSIDE WALL) TERMINATION

SYSTEM

See Figures 27, and Figures 30 to 33 on Pages

18, 20 and 21 and their associated Horizontal

Vent Table which illustrate the various horizontal

venting configurations that are possible for use

with these appliances. Secure Vent™ pipe ap-

plications are shown in these figures; Secure

Flex™ pipe may also be used. A Horizontal Vent

Table summarizes each system’s minimum and

maximum vertical and horizontal length values

that can be used to design and install the vent

components in a variety of applications.

Both of these horizontal vent systems terminate

through an outside wall. Building Codes limit or

prohibit terminating in specific areas. Refer to

Figure 7 on Page 7 for location guidelines.

Secure Vent SV4.5 direct-vent system compo-

nents are unitized concentric pipe components

featuring positive twist lock connection, (refer

to Figure 18 on Page 15). All of the appli-

ances covered in this document are fitted with

collars having locking inclined channels. The

dimpled end of the vent components fit over

the appliance collar to create the positive twist

lock connection.

A. Plan the vent run -

Analyze the vent routing and determine the

types and quantities of sections required 4-

1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572

mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm)

net section lengths are available. It is recom-

mended that you plan the vent lengths so that a

joint does not occur at the intersection of ceiling

or roof joists. Make allowances for elbows as

indicated in Figure 20 on Page 16.

Maintain a minimum 1" (25 mm) clearance to

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; 3" (76 mm)

on top, 1" (25 mm) on sides, and 1" (25 mm)

at the bottom.

B. Frame exterior wall opening -

Locate the center of the vent outlet on

the exterior wall according to the dimen-

sions shown in Figure 12 on Page 10. Cut

and/or frame an opening, 10-1/2" x 12-1/8"

(267 mm x 308 mm) inside dimensions, about

this center.

C. Frame ceiling opening - If the vertical route

is to penetrate a ceiling, use plumb line to locate

the center above the appliance. Cut and/or frame

an opening, 10-1/2" x 10-1/2" (267 mm x 267

mm) inside dimensions, about this center (refer

to Figure 17 on Page 15).

D. Attach vent components to appliance - To

attach a vent component to the appliance collar,

align the dimpled end over the collar, adjust-

ing the radial alignment until the four locking

dimples are aligned with the inlets of the four

incline channels on the collar (refer to Figure

18 on Page 15).

Push the vent component against the collar

until it fully engages, then twist the component

clockwise, running the dimples down and along

the incline channels until they seat at the end

of the channels. The unitized design of the

Secure Vent components will engage and seal

both the inner and outer pipe elements with the

same procedure. Sealant and securing screws

are not required.

Note: An elbow may also be attached to the

appliance collar. Attach in the same manner

as you would a vent section.

E. Attach vent components to each other

- Other vent sections may be added to the

previously installed section in accordance with

the requirements of the vent tables. To add

another vent component to a length of vent

run, align the dimpled end of the component

over the inclined channel end of the previously

installed section, adjusting the radial alignment

until the four locking dimples are aligned with

the inlets of the four incline channels of the

previous section.

Push the vent component against the previous

section until it fully engages, then twist the

component clockwise running the dimples

down and along the incline channels until they

seat at the end of the channels. This seating

position is indicated by the alignment of the

arrow and dimple as shown in Figure 18 on

Page 15.

F. Install firestop/spacer at ceiling -

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex,

use SF4.5VF firestop/spacer. If there is living

space above the ceiling level, the firestop/

spacer must be installed on the bottom side of

the ceiling. If attic space is above the ceiling, the

firestop/ spacer must be installed on the top side

of the joist. Route the vent sections through the

framed opening and secure the firestop/spacer

with 8d nails or other appropriate fasteners at

each corner.

Figure 27

Support the vertical portion of the venting system

every 8 feet (2.4m) above the fireplace vent outlet.

Ceiling

Fireplace

Vertical

Rise

SV4.5 HT-2

Termination

Shown

Support Bracket Spacing

Every 5 ft (1.52 m)

SV4.5 HT-2

Termination

Shown

Support Brackets

Building

Support

Framing

Horizontal / Inclined Run

SV4.5E90

Elbow

See Figure 19 on Page 15 for vertical

vent section support.

u

When Using Secure Flex,

Use Firestop / Spacer SF4.5VF

u

Firestop / Spacer

SV4.5VF

SV4.5L6/12/24/36/48

Vent Sections

Exterior

Wall

Advertising
This manual is related to the following products: