LST GD-55000-127 User Manual

Specifi cations

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

GD-55000-127_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

• Addressable conventional technology
• Maximum temperature 78°C
• Individual detector addressing by

means of optional address module

• Optional connection of remote

indicator

• Sealed electronics

Description

The Thermal ROR Detector GD-55000-127 reacts to

temperature changes within defi ned periods of time,

up to a maximum temperature of 78°C. The intelligent

evaluation of these data allows the early detection of

spreading fi res. The detector complies with Class BR

and can be used up to a room height of 6m.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. By

means of the optional Address Module NG60-1, each

detector can be addressed individually. With that, the

activated detector can also be safely identifi ed directly

on the control panel.

The detector can be attached to various bases and it

can be protected against theft.

Specifi cations

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 45µA (quiescent)

Alarm temperature

78°C (maximum-heat component)

Operating temperature

max. +65°C

Ambient temperature

-20°C to +90°C (no condensation or icing)

Relative humidity

0 – 95% (no condensation)

Dimensions ш Ч H

100 × 42 (mm)

Colour

white

Weight

80g

Approval

VdS G200060

Order number

242025

Order name

Thermal ROR Detector/Conv./65/Apo GD-55000-127

Advertising