Troubleshooting, Caution – Lincoln Electric SAE-400 SEVERE DUTY IM727 User Manual

Page 26

Advertising
background image

E-4

TROUBLESHOOTING

E-4

SAE-400 SEVERE DUTY

Observe all Safety Guidelines detailed throughout this manual

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your

Local

Lincoln Authorized Field Service Facility

for technical troubleshooting assistance before you proceed.

CAUTION

PROBLEMS

(SYMPTOMS)

POSSIBLE AREAS OF

MISADJUSTMENT(S)

RECOMMENDED

COURSE OF ACTION

Welding current too great or too
small compared to indication on the
dial.

Welder has output and no control

No auxiliary power

1.

Current Control

shaft and han-

dle may have turned slightly in
the insulated bushing of the cur-
rent control brushholder, caused
by turning handle too hard against
one of the stops.

2. Exciter output low causing low

output compared to dial indica-
tion.

3.

Current Control

set to minimum

and welder output so great that
engine stalls when arc is struck.

1. Local/Remote switch is in wrong

position.

1. GFCI Receptacle may have

tripped. Follow

GFCI Receptacle

Testing and Resetting Procedure

in the MAINTENANCE section of
this manual. (GFCI Receptacle is
Optional)

2. Circuit Breakers open.

3. Faulty connections to auxiliary

receptacles.

4. Faulty receptacles.

If all recommended possible areas
of misadjustment have been
checked and the problem persists,

Contact your local Lincoln
Authorized Field Service Facility.