FLEXTEC™ 450

A-1

INSTALLATION

A-1

TECHNICAL SPECIFICATIONS -

FLEXTEC™ 450

RATED OUTPUT

POWER SOURCE-INPUT VOLTAGE AND CURRENT

Model

K2882-1

Duty Cycle

60% rating

100% rating

Volts at Rated Amperes

36.5V

34V

28V

26V

38V

36V

36.5V

34V

36.5V

34V

Amperes

450

400

450

400

450

400

450

400

450

400

Duty Cycle

60%

100%

60%

100%

60%

100%

60%

100%

60%

100%

Process

GMAW (CV)

GTAW (CC)

SMAW (CC)

FCAW-GS (CV)

FCAW-SS (CV)

Input Amperes

37 / 27 / 22

29 / 21 / 17

Idle Power

72 Watts

Max.

(fan on)

Power Factor @

Rated Output

95%

Input Voltage ± 10%

380 / 460 / 575 / 3 / 50 / 60

(1) Cord and Fuse Sizes based upon the U.S. National Electric Code and maximum output for 40°C (104°) ambient.
(2) Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers that have a delay in tripping action that decreases as the

magnitude of current increases.

(3) Type SD cord or similar in 30°C ambient.

VOLTAGE

50/60Hz

380/3/50
460/3/60
575/3/60

Maximum

Input

Amperes

42 A
30 A
25 A

Cord Size

(3)

AWG SIzES

(mm)

8(10)
8(10)
10(6)

Fuse (Super Lag) or

Breaker Size

(2)

50
45
35

COPPER GROUNDING

CONDUCTOR

AWG (mm

2

)

10 (6)
10 (6)
12 (4)

Type 75°C Copper

Wire in Conduit

AWG (mm

2

)

8 (10)
10 (6)
12 (4)

RECOMMENDED INPUT WIRE AND FUSE SIzES