A

Building Safety. Building Security.

• Up to 32 radio detectors can be

controlled

• Radio detectors can be assigned to 2

detector zones

• Individual detector identifi cation

display via 32 LEDs

• High range of radio transmission
• Two frequency bands (868/434MHz)

with automatic change-over

• Channel checked for availability

Description

Specifi cations

Mains voltage

230VAC +10/-15%, 50Hz

Connection power

12VA

External supply voltage (supply through external power unit)

10 – 30VDC

Current consumption at 12V (supply through external power unit)

max. 110mA (quiescent), 120mA (alarm)

Range of radio transmission (free air)

400m

Frequency band

868MHz or 434MHz

Ambient temperature

0°C to +60°C

Dimensions W × H × D

300 Ч 390 Ч 140 (mm)

Colour

white

Weight (without battery)

8.7kg

Approval

VdS G206015

Order number

249201

Order name

RF Interface/4Rel FUIF511-27D

The RF Interface FUIF511-27D serves for the connec-

tion of up to 32 automatic or manual radio detectors.

The interface is provided with two detector zones, each

of them having separate alarm and fault detection re-

lays. Up to 16 detectors can be assigned to each zone.

The two zones can be reported to the fi re detection

control panel as collective messages, either in conven-

tional technology or by means of auxiliary modules via

the ADM loop. After an alarm activation the RF interface

can be reset by the fi re detection control panel, via the

remote reset input.

The detectors are programmed (learned) at the RF inter-

face by using built-in keys. For each radio component

the receiver unit provides an individual LED indicator.

If necessary, several radio detection systems can be

used in the same building, in order to integrate more

than 32 radio components or to create more than 2

detector zones. A unique key, based on a choice of

several million codes, is created, which ensures the

unambiguous identifi cation of the detectors.

The RF Interface FUIF511-27D is equipped with a power

unit and can be protected against a power failure by

means of a stand-by battery 7Ah. It is also possible to

use an external power supply.