Refrigerator installation – LG Side By Side Refrigerator LSC27925** User Manual

Page 10

Advertising
background image

10

• Two 1/4” (6,35 mm) outer

diameter compression nuts

and 2 ferrules (sleeves) to

connect the copper tubing

to the shutoff valve and the

refrigerator water valve.

If your existing copper water line has a

flared fitting at the end, you will need

an adapter (available at plumbing

supply stores) to connect the water

line to the refrigerator OR you can cut

off the flared fitting with a tube cutter and then use a

compression fitting.

• Shutoff valve to connect

to the cold water line. The

shutoff valve should have a

water inlet with a minimum

inside diameter of 5/32”

(3,96 mm) at the point of

connection to the COLD WATER LINE. Saddle-type

shutoff valves are included in many water supply kits.

Before purchasing, make sure a saddle-type valve

complies with your local plumbing codes.

INSTALLATION INSTRUCTIONS

WARNING: Connect to potable water supply only.

1. SHUTOFF THE MAIN WATER SUPPLY

Turn on the nearest faucet to relieve the pressure on the

line.

2. CHOOSE THE VALVE LOCATION

Choose a location for the valve that is

easily accessible. It is best to connect into

the side of a vertical water pipe. When it

is necessary to connect into a horizontal

water pipe, make the connection to the

top or side, rather than at the bottom, to

avoid drawing off any sediment from the

water pipe.

3. DRILL THE HOLE FOR THE VALVE

Drill a 1/4” (6,35 mm) hole in

the water pipe using a sharp bit.

Remove any burrs resulting from

drilling the hole in the pipe. Take

care not to allow water to drain

into the drill. Failure to drill a 1/4”

(6,35 mm) hole may result in

reduced ice production or smaller

cubes.

NOTE: Licensed plumbers MUST use only cooper

tubing NDA tubing #49595 or 49499 or Cross

Link Polyethylene (PEX) tubing.

4. FASTEN THE SHUTOFF VALVE

Fasten the shutoff valve to the cold water pipe with the

pipe clamp.

NOTE: Commonwealth of Massachusetts Plumbing

Codes 248CMR shall be adhered to. Saddle valves

are illegal and use is not permitted in Massachusetts.

Consult with your licensed plumber.

5. TIGHTEN THE PIPE CLAMP

Tighten the clamp screws until the sealing washer begins

to swell.

NOTE: Do not overtighten or you may crush the tubing.

6. ROUTE THE TUBING

Route the tubing between the cold water line and the

refrigerator.

Route the tubing through a hole drilled in the wall or

floor (behind the refrigerator or adjacent base cabinet)

as close to the wall as possible.

NOTE: Be sure there is sufficient extra tubing [about

8 feet (2,4 m) coiled into 3 turns of about 10”

(25 cm) diameter] to allow the refrigerator to

move out from the wall after installation.

7. CONNECT THE TUBING TO THE VALVE

Place the compression nut and ferrule (sleeve) for copper

tubing onto the end of the tubing and connect it to the

shutoff valve. Make sure the tubing is fully inserted into

the valve. Tighten the compression nut securely.

REFRIGERATOR INSTALLATION

REFRIGERATOR INSTALLATION

Pipe Clamp

Saddle-Type

Shutoff Valve

Vertical Cold

Water Pipe

Pipe Clamp

Clamp Screw

Washer

Inlet End

Advertising